Specifications
Original instructions
General Specifications
General Specifications
Module Type
16 IN (2 groups x 8 points)
External Power
Not required for this module
Power Dissipation
5.5 W (max)
Bus Current required
180 mA
I/O map
1 input word
Fault Detection
None
Operating Voltage and Input Current*
Operating Voltage and Input Current*
50 Hz
ON: 85 ... 132 VAC (11.1 mA max)
OFF: 0 ... 20 VAC
60 Hz
ON: 79 ... 132 VAC (13.2 mA max)
OFF: 0 ... 20 VAC
* Do not use outside the 47 ... 63 Hz range
Maximum Allowable Leakage Current from an External Device to be recognized as an OFF Condition.
2.1 mA
Typical Input Impedance
Typical Imput Impedance
50 Hz
14.4 kohms capacitive
60 Hz
12 kohms capacitive
Isolation
Isolation
Group to Group
1780 VAC for 1 minute
Input to Bus
1780 VAC for 1 minute
Absolute Maximum Input
Absolute Maximum Input
Continuous
132 VAC
10 s
156 VAC
1 Cycle
200 VAC
1.3 ms
276 VAC
Response
Response
OFF - ON
Min: 4.9 ms. Max: 0.75 line cycle.
ON - OFF
Min: 7.3 ms. Max: 12.3 ms.
Fuses
Fuses
Internal
None
External
User installed per local and national electrical codes
NOTE: Input signals must be sinusoidal with less than 6% THD and 63 Hz maximum frequency.