Specifications
Original instructions
General Specifications
General Specifications
Module Type
32 IN (4 groups x 8 points)
External Power
Not required for this module
Power Dissipation
10.9 W (max.)
Bus Current required
250 mA
I/O map
2 input words
Fault Detection
None
Operating Voltage and Input Current*
Operating Voltage and Input Current*
50 Hz
ON: 14 ... 30 VAC (11.1 mA max)
OFF: 0 ... 5 VAC
60 Hz
ON: 12 ... 30 VAC (13.2 mA max)
OFF: 0 ... 5 VAC
* Do not use outside the 47 ... 63 Hz range
Maximum Allowable Leakage Current from an External Device to be recognized as an OFF Condition.
1.9 mA
Typical Input Impedance
Typical Imput Impedance
50 Hz
3.1 kohms capacitive
60 Hz
2.6 kohms capacitive
Isolation
Isolation
Group to Group
1780 VAC for 1 minute
Input to Bus
1780 VAC for 1 minute
Fuses
Fuses
Internal
None
External
User installed per local and national electrical codes
Absolute Maximum Input
Absolute Maximum Input
Continuous
30 VAC
10 s
32 VAC
1 Cycle
50 VAC
Response
Response
OFF - ON
Min: 4.9 ms. Max: 0.75 line cycle.
ON - OFF
Min: 7.3 ms. Max: 12.3 ms.
NOTE: Input signals must be sinusoidal with less than 6% THD and 63 Hz maximum frequency.