Module Type
|
16 IN (16 groups x 1 point) individually isolated
|
External Power
|
Not required for this module
|
Power Dissipation
|
5.5 W (max.)
|
Bus Current required
|
180 mA
|
I/O map
|
1 input word
|
Fault Detection
|
None
|
47 - 53 Hz
|
ON: 18 ... 30 VAC (10.7 mA max.)
OFF: 0 ... 5 VAC
|
57 - 63 Hz
|
ON: 16 ... 30 VAC (12 mA max.)
OFF: 0 ... 6 VAC
* Do not use outside the 47 ... 63 Hz range
|
Maximum Allowable Leakage Current from an External Device to be recognized as an OFF Condition.
|
1.9 mA
|
50 Hz
|
3.1 kohms capacitive
|
60 Hz
|
2.6 kohms
|
Input to Input
|
1780 VAC for 1 minute
|
Input to Bus
|
1780 VAC for 1 minute
|
Continuous
|
30 VAC
|
10 s
|
32 VAC
|
1 Cycle
|
50 VAC
|
OFF - ON
|
Min: 4.9 ms. Max: 0.75 line cycle.
|
ON - OFF
|
Min: 7.3 ms. Max: 12.3 ms.
|
Internal
|
None
|
External
|
User installed per local and national electrical codes
|