Module Type
|
32 IN (4 groups x 8 points)
|
Logic
|
True High
|
External Power
|
10 ... 60 VDC (group supply)
|
Power Dissipation
|
1.0 W + 0.25 W x the number of points ON
|
Bus Current required
|
300 mA
|
I/O map
|
2 input words
|
Fault Detection
|
None
|
Group supply / Tolerance
|
ON* State
|
OFF* State
|
12 VDC / +/-5%
|
9 ... 12 VDC
|
0 ... 1.8 VDC
|
24 VDC / -15% ... +20%
|
11 ... 24 VDC
|
0 ... 5 VDC IEC61131
|
48 VDC / -15% ... +20%
|
34 ... 48 VDC
|
0 ... 10 VDC IEC61131
|
60 VDC / -15% ... +20%
|
45 ... 60 VDC
|
0 ... 12.5 VDC
*ON / OFF state ranges are specified at nominal reference voltages.
|
Group to Group
|
700 VDC for 1 minute
|
Group to Bus
|
2500 VDC for 1 minute
|
Absolute Maximum Input
|
75 VDC
|
Input Protection
|
Resistor Limited
|
@ 12 VDC
|
5 ... 10 mA
|
@ 24 VDC
|
6 ... 30 mA
|
@ 48 VDC
|
2 ... 15 mA
|
@ 60 VDC
|
1 ... 5 mA
|
OFF - ON
|
4 ms
|
ON - OFF
|
4 ms
|
Switching Frequency
|
< 100 Hz max.
|
Internal
|
None
|
External
|
User installed per local and national electrical codes
|