Module Type
|
32 IN (4 groups x 8 points)
|
Logic
|
True Low
|
External Power
|
19.2 ... 30 VDC
|
Power Dissipation
|
1.5 W + 0.26 W x the number of points ON
|
Bus Current required
|
330 mA max.
|
I/O map
|
2 input words
|
Fault Detection
|
None
|
Group to Group
|
500 VAC rms for 1 minute
|
Group to Bus
|
1780 VAC rms for 1 minute
|
ON Level voltage
|
-15 ... -30 VDC (reference from group supply)
|
OFF Level voltage
|
0 ... -5 VDC (reference from group supply)
|
ON Level current
|
2.0 mA min; 14 mA max
|
OFF Level current
|
0.5 mA max
|
Internal Resistance
|
2.4 kohm
|
Input Protection
|
Resistor Limited
|
Continuous
|
30 VDC
|
1.3 ms
|
50 VDC decaying pulse
|
OFF - ON
|
1 ms (max)
|
ON - OFF
|
1 ms (max)
|
Internal
|
None
|
External
|
User installed per local and national electrical codes
|