Wiring Diagram
Original instructions
Illustration
WARNING
UNINTENDED EQUIPMENT OPERATION
Before removing the connector, remove the field power or ensure that the pre-actuator wiring can remain in an open circuit condition.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The following figure shows the wiring diagram for the 140 ACO 020 00 module.
External Wiring Recommendation
  1. The user supplies the current and voltage sources (installation and calibration of fuses are at the discretion of the user).
  2. Use shielded signal cable. In noisy environnements, twisted shielded cable is recommended.
  3. Shielded cables should be connected to the PLC’s ground.
  4. A Shield Bar (STB XSP 3000 and STB XSP 3010/3020) should be used to connect the shielded cable to ground.
  5. Unused channels indicate broken wire status unless wired to the loop supply, as shown on Channel 4. In this example, loop supply must be 30 V or less
  6. The wiring example shows Channel 1 acting as a current sink and Channel 2 acting as a current source for their respective field devices.
  7. N / C = Not Connected.
NOTE: VM is an optional voltmeter that can be connected to read voltage that is proportional to the current. Wiring to this terminal is limited to 1 meter maximum.
NOTE: When field wiring the I/O module, the maximum wire size that should be used is 1-14 AWG or 2-16 AWG; the minimum size is 20 AWG.
NOTE: The tightening torque must be between 0.5 Nm and 0.8 Nm.
NOTICE
DESTRUCTION OF ADAPTER
  • Before tightening the locknut to the torque 0.50...0.80 Nm, be sure to properly position the right-angle F adapter connector.
  • During tightening, be sure to maintain the connector securely.
  • Do not tighten the right-angle F adapter beyond the specified torque.
Failure to follow these instructions can result in equipment damage.