Wiring Diagram
Original instructions
Illustration
Wiring diagram for the 140 ACI 040 00 Module.
External Wiring Recommendations
  1. The user supplies the current and voltage sources (installation and calibration of fuses are at the discretion of the user).
  2. Use shielded signal cable. In noisy environnements, twisted shielded cable is recommanded.
  3. Shielded cables should be connected to the PLC’s ground.
  4. A Shield Bar (STB XSP 3000 and STB XSP 3010/3020) should be used to connect the shielded cable to ground.
  5. The maximum channel to channel working voltage cannot exceed 30 Vdc.
  6. N / C = Not connected.
NOTE: When field wiring the I/O module, the maximum wire size that should be used is 1-14 AWG or 2-16 AWG; the minimum size is 20 AWG.
NOTE: The tightening torque must be between 0.5 Nm and 0.8 Nm.
NOTICE
DESTRUCTION OF ADAPTER
  • Before tightening the locknut to the torque 0.50...0.80 Nm, be sure to properly position the right-angle F adapter connector.
  • During tightening, be sure to maintain the connector securely.
  • Do not tighten the right-angle F adapter beyond the specified torque.
Failure to follow these instructions can result in equipment damage.