Checking the Discrete Input / Output connection
(Original Document)
At a Glance
In order to check the Discrete I/O connection, ensure that:
WARNING
UNEXPECTED SYSTEM BEHAVIOR
Active outputs can activate machine movements.
Turn all power off before checking the Discrete I/O connection:
  • remove power fuses from the motor controls,
  • shut off the hydraulic and pneumatic units,
  • then power up the PLC fitted with its Discrete I/O modules.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Description
It is possible to check the connection of the Discrete I/O modules:
Input check
The following table shows the procedure for checking input connections.
Step
Action
1
Activate each sensor and check that the corresponding input LED changes status.
2
Check on the terminal screen that the corresponding input bit (%I•) also changes status.
Output check
The following table shows the procedure for checking output connections.
Step
Action
1
From the terminal, set each bit (%Q•) that corresponds to an output to 1 then 0.
2
Check that the corresponding output LED turns on then off and that the corresponding pre-actuator activates then de-activates.