Type of module
|
Transistor outputs with screw terminal block connection
|
||||
Illustration
|
Discrete output module
![]() |
Discrete output module
![]() |
Discrete output module
![]() |
Discrete output module
![]() |
Discrete output module
![]() |
Number of channels
|
8 outputs
|
16 outputs
|
|||
Range
|
24 VDC
|
48 VDC
|
24 VDC
|
48 VDC
|
|
Insulation
|
Insulated outputs
|
||||
Current
|
0.5 A
|
2 A
|
1 A
|
0.5 A
|
0.25 A
|
IEC 1131-2 compliance
|
Yes
|
||||
Protection
|
Outputs protected against short-circuits and overloads, with automatic or controlled reactivation, and with fast electromagnet demagnetization circuits.
|
||||
Fallback
|
Configurable fallback of outputs, permanent monitoring of output control, and reset of outputs in the event of detection of an internal fault.
|
||||
Logic
|
Positive
|
||||
Response time
|
1 ms
|
0.2 ms
|
0.3 ms
|
1 ms
|
1 ms
|
Connections
|
Screw terminal block
|
||||
TSX•• reference number
|
DSY 08T2
|
DSY 08T22
|
DSY 08T31
|
DSY 16T2
|
DSY 16T3
|
Type of module
|
Relay outputs with screw terminal block connection
|
|||
Illustration
|
Discrete module
![]() |
Discrete output module
![]() |
Discrete module
![]() |
|
Number of channels
|
8 outputs
|
16 outputs
|
||
Range
|
12..24 VDC or 24..240 VAC
|
24..130 VDC
|
24..48 VDC or 24..240 VAC
|
12..24 VDC or 24..240 VAC
|
Insulation
|
Outputs insulated between contact and earth
|
|||
Current
|
3 A
|
5 A
|
3 A
|
|
IEC 1131-2 compliance
|
Yes
|
|||
Protection
|
No protection
|
Interchangeable fuse protection. Output reset in the event of fault detection, reactivation once fuse is replaced.
|
No protection
|
|
Fallback
|
Configurable output fallback.
|
|||
Terminal block unlocking
|
Automatic output cut-off device on unlocking of terminal blocks.
|
|||
Logic
|
Positive/negative
|
|||
Connections
|
Screw terminal block
|
|||
TSX•• reference number
|
DSY 08R5
|
DSY 08R4D
|
DSY 08R5A
|
DSY 16R5
|
Type of module
|
Bidirectional triode thyristor outputs with screw terminal block connection
|
||
Illustration
|
Discrete output module
![]() |
Discrete output module
![]() |
Discrete output module
![]() |
Number of channels
|
8 outputs
|
16 outputs
|
|
Range
|
48..240 VAC
|
24..120 VAC
|
|
Insulation
|
Insulated outputs
|
||
Current
|
2 A
|
1 A
|
|
IEC 1131-2 compliance
|
Yes
|
||
Protection
|
Interchangeable fuse protection.
|
Outputs not protected against short circuits or overloads. ’Fireproof’ protection via non-interchangeable fuses
|
|
Fallback
|
Configurable output fallback.
|
||
Terminal block unlocking
|
Automatic output cut-off device on unlocking of terminal blocks.
|
||
Connections
|
Screw terminal block
|
||
TSX•• reference number
|
DSY 08S5
|
DSY 16S5
|
DSY 16S4
|
Type of module
|
Transistor outputs with HE10 connectors.
|
|
Illustration
|
Discrete output module
![]() |
Discrete output module
![]() |
Number of channels
|
32 outputs
|
64 outputs
|
Range
|
24 VDC
|
|
Insulation
|
Insulated outputs
|
|
Current
|
0.1 A
|
|
IEC 1131-2 compliance
|
Yes
|
|
Protection
|
Outputs protected against short circuits and overloads with automatic or controlled reactivation.
|
|
Fallback
|
Configurable fallback of outputs, permanent monitoring of output control, and reset of outputs in the event of detection of an internal fault.
|
|
Logic
|
Positive
|
|
Connections
|
HE 10 connector
|
|
TSX•• reference number
|
DSY 32T2K
|
DSY 64T2K
|