Characteristics of the Removable ABS-7Sxx Static Output Relays
(Original Document)
At a Glance
The general characteristics of the removable ABS-7S•• static output relays for TELEFAST 2 bases are described in this section.
General Characteristics
This table shows the general characteristics of the ABS-7S•• relays.
ABS-7S•• reference
C2E
A2M
C3BA
C3E
A3M
Relay width
10 mm
12.5 mm
Output circuit characteristics
Voltage assigned to job
Direct
5..48 V
-
24 V
5..48 V
-
Alternating
-
24..240 V
-
24..240 V
Max. voltage
57.6 VDC
264 VAC
30 VDC
60 VDC
264 VAC
Alternating current load
Resistive, load AC12
Current
-
0.5 A
-
2 A
Direct current load
Resistive, load DC12
Current
0.5 A
-
2 A
1.5 A
-
Inductive load DC13
Current
-
-
0.3 A
-
Filament lamp load DC6
-
10 W
-
Leakage current at state 0
<= 0.5 mA
<= 2 mA
<= 0.3 mA
<= 2 mA
Breakdown voltage at state 1
<= 1 V
<= 1.1 V
<= 0.3 V
<= 1.3 V
Minimum current through channel
1 mA
10 mA
1 mA
10 mA
Response time
State 0 to 1
0.1 ms
10 ms
0.1 ms
10 ms
State 1 to 0
0.6 ms
10 ms
0.02 ms
0.6 ms
10 ms
Switching frequency on inductive load
-
< 0.5 LI2
-
Voltage assigned to insulation
Input/output
300 V
Voltage assigned to shock resistance (1.2/50)
Input/output
2.5 kV