MOD_FLT Byte in Device DDT

MOD_FLT byte structure:

Bit

Symbol

Description

0

MOD_FAIL

  • 1: Internal detected error or module failure detected.

  • 0: No detected error

1

CH_FLT

  • 1: Inoperative channels.

  • 0: Channels are operative.

2

BLK

  • 1: Terminal block detected error.

  • 0: No detected error.

NOTE: This bit may not be managed.

3

  • 1: Module in self-test.

  • 0: Module not in self-test.

NOTE: This bit may not be managed.

4

Not used.

5

CONF_FLT

  • 1: Hardware or software configuration detected error.

  • 0: No detected error.

6

NO_MOD

  • 1: Module is missing or inoperative.

  • 0: Module is operating.

NOTE: This bit is managed only by modules located in a remote rack with a BME CRA 312 10 adapter module. Modules located in the local rack do not manage this bit that remains at 0.

7

Not used.