Module level constants

The table following presents the %KW common for each channel group of the module:

Object

Type

Detail

Channel group

%KWr.m.c.0

with c = 0, 8, 16, 24, 32, 40, 48, 56.

INT

For each channel group

bit 0: Validation input function = 1

bit 1: Validation output function = 1

bit 2: Strategy of fallback: 1 = get value, 0 = stay at current value

bit 3: Input filtering (1 = fast, 0 = normal), fixed at 0

bit 4: Ouput protection (1 = yes, 0 = no)

bit 5: Rearm outputs: 1 = automatic, 0 = by command

bit 6: Not used

bit 7: Power supply control inhibition (1 = yes, 0 = 0)

0-7 1 st grp

8-15 2 nd grp

16-23 3 rd grp

24-31 4 th grp

32-39 5 th grp

40-47 6 th grp

48-55 7 th grp

56-63 8 th grp

     

Fallback value (ouputs) or sensor type (inputs) for channel:

   

bit 8

0

8

16

24

32

40

48

56

   

bit 9

1

9

17

25

33

41

49

57

   

bit 10

2

10

18

26

34

42

50

58

   

bit 11

3

11

19

27

35

43

51

59

   

bit 12

4

12

20

28

36

44

52

60

   

bit 13

5

13

21

29

37

45

53

61

   

bit 14

6

14

22

30

38

46

54

62

   

bit 15

7

15

23

31

39

47

55

63

%KWr.m.c.1

INT

                 

byte 0

byte

 

Validation of Input/output open line control for channel:

bit 0

0

8

16

24

32

40

48

56

bit 1

1

9

17

25

33

41

49

57

bit 2

2

10

18

26

34

42

50

58

bit 3

3

11

19

27

35

43

51

59

bit 4

4

12

20

28

36

44

52

60

bit 5

5

13

21

29

37

45

53

61

bit 6

6

14

22

30

38

46

54

62

bit 7

7

15

23

31

39

31

55

63

byte 1

byte

 

Validation of value memorization for channel:

bit 8

0

8

16

24

32

40

48

56

bit 9

1

9

17

25

33

41

49

57

bit 10

2

10

18

26

34

42

50

58

bit 11

3

11

19

27

35

43

51

59

bit 12

4

12

20

28

36

44

52

60

bit 13

5

13

21

29

37

45

53

61

bit 14

6

14

22

30

38

46

54

62

bit 15

7

15

23

31

39

47

55

63

%KWr.m.c.2

INT

                 

byte 0

byte

not used

byte 1

byte

not used

There are one %KWr.m.c.0, one %KWr.m.c.1 and one %KWr.m.c.2 common for all channels for a group in this FB_type

NOTE: It is not possible to configure a module by programming using direct language objects %KW; these words are accessible in read only format.