Altitude Operating Conditions
The characteristics in the table below apply to the modules BMX DDO 1612 and BMX DDO 1612H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
This table presents the general characteristics for the BMX DDO 1612 and BMX DDO 1612H modules:
Module type |
24 VDC negative logic static outputs |
||
Operating temperature |
BMX DDO 1612 |
0...60 ºC (32...140 ºF) |
|
BMX DDO 1612H |
-25...70 ºC (-13...158 ºF) |
||
Temperature derating |
Apply the temperature derating curve |
||
Nominal values |
Voltage |
24 VDC |
|
Current |
0.5 A |
||
Threshold values |
Voltage (including ripple) |
19...30 V (34 V possible for 1 hour/day) |
|
Current/channel |
0.625 A |
||
Current/module |
10 A |
||
Power of tungsten filament lamp |
Maximum |
6 W |
|
Leakage current |
At 0 |
< 0.5 mA |
|
Residual voltage |
At 1 |
< 1.2 V |
|
Load impedance |
minimum |
48 Ω |
|
Response time(1) |
1.2 ms |
||
Reliability |
MTBF for continuous operation in hours at ambient temperature 30 °C (86 °F) |
403 804 |
|
Frequency of switching to inductive load |
0.5 / LI2 Hz |
||
Paralleling of outputs |
Yes (maximum of 3) |
||
Compatibility with DC inputs |
Yes (source and no type inputs) |
||
Built-in protection(2) |
against over voltage |
Yes, by Transil diode |
|
against reverse polarity |
Yes, by reverse-mounted diode |
||
against short-circuits and overloads |
Yes, by current limiter and electric circuit-breaker 1.5 In < Id < 2 In |
||
Fuse type |
Internal |
None |
|
External |
1 fast blow fuse of 6.3 A |
||
Pre-actuator voltage: monitoring threshold |
OK |
> 18 V |
|
Error |
< 14 V |
||
Pre-actuator voltage: monitoring response time |
on appearance |
8 ms < T < 30 ms |
|
on disappearance |
1 ms < T < 3 ms |
||
Power consumption 3.3 V |
typical |
79 mA |
|
maximum |
111 mA |
||
24 V pre-actuator consumption (Excluding load current) |
typical |
23 mA |
|
maximum |
32 mA |
||
Power dissipation |
2.26 W max. |
||
Dielectric strength |
Output / ground or output / internal logic |
1500 V rms, 50 / 60 Hz for 1 min. |
|
Resistance of insulation |
>10 MΩ (below 500 VDC) |
||
(1) All outputs are equipped with fast demagnetization circuits for electromagnets. Electromagnet discharge time < L/R. (2) Provide a fuse to the +24 V pre-actuator supply. |