Altitude Operating Conditions

The characteristics in the table below apply to the modules BMX DAO 1605 and BMX DAO 1605H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.

For detailed information, refer to chapter Operating and Storage Conditions.

General Characteristics

This table presents the general characteristics for the BMX DAO 1605 and BMX DAO 1605H modules:

Module type

100...240 VAC triac outputs

Operating temperature

BMX DAO 1605

0...60 ºC (32...140 ºF)

BMX DAO 1605H

-25...70 ºC (-13...158 ºF)

Temperature derating

Apply the temperature derating curve

Nominal values

Voltage

100...240 VAC

Current

0.6 A / points

Threshold values

Voltage

100 mA at 24 VAC

25 mA at 100...240 VAC

Current/channel

0.6 A

Current/module

2.4 A max/common (4.8 A max for all commons)

Maximum inrush current

20 A / cycle or less

Leakage current

At state 0

≤ 3 mA (for 240 VAC, 60 Hz)

≤ 1.5 mA (for 120 VAC, 60 Hz)

Residual voltage

At state 1

≤ 1.5 VAC

Response time

≤ 1 ms + 1/(2xF)

Built-in protection

Against inductive over voltage in AC modes

None. Fit an RC circuit or a ZNO type over voltage limiter in parallel on each output appropriate to the voltage in use

Against inductive over voltage

None. Fit a discharge diode on each output.

against short-circuits and overloads

None. Fit a fast-blow fuse of 3 A on each channel or 4-channel group.

Command type

Zero crossing

Output protection

no protection

Dielectric maximum voltage

2 830 VAC rms/1 min

Insulation resistance

≥ 10 MΩ (by insulation resistance meter)

Noise immunity

By noise simulator of noise voltage, 1 μs noise width and 1 500 Vp-p

25...60 Hz noise frequency

Power consumption 3.3 V

Typical

79 mA

Maximum

111 mA

NOTE: For the BMX DAO 1605H module, at 70 °C (158 °F), the maximum threshold current must not exceed 0.24 A per channel and the maximum module current must not exceed 1.92 A.