Altitude Operating Conditions
The characteristics in the table below apply to the modules BMX DRA 1605 and BMX DRA 1605H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
This table presents the general characteristics for the BMX DRA 1605 and BMX DRA 1605H modules:
Module type |
Relay outputs for alternating and direct current |
|||||
Operating temperature |
BMX DRA 1605 |
0...60 ºC (32...140 ºF) |
||||
BMX DRA 1605H |
-25...70 ºC (-13...158 ºF) |
|||||
Rated voltage |
Direct |
24 VDC |
||||
Alternating |
24...240 VAC / 2 A, Cos ? = 1 |
|||||
Voltage range |
Direct |
24 VDC / 2 A (resistive load) |
||||
Alternating |
19...264 VAC / 2 A, Cos ? = 1 |
|||||
Minimum switching load |
5 VDC / 1 mA. |
|||||
Maximum switching load |
264 VAC / 125 VDC |
|||||
Mechanical service life |
Number of switching |
20 million or more |
||||
Alternating current load in resistive mode (AC12) |
Voltage |
24 VAC |
48 VAC |
100...120 VAC |
200...240 VAC |
|
Power |
50 VA(2) |
50 VA(1) 80 VA(2) |
80 VA(1) 200 VA(2) |
200 VA(1) |
||
Alternating current load in inductive mode (AC15) |
Voltage |
24 VAC |
48 VAC |
100...120 VAC |
200...240 VAC |
|
Power |
36 VA(1) 72 VA(1) 120 VA(2) |
36 VA(1) 72 VA(1) 120 VA(2) |
36 VA(1) 72 VA(1) 120 VA(2) |
36 VA(1) Cos ? = 0,35 72 VA(1) Cos ? = 0,7 120 VA(2) Cos ? = 0,35 240 VA(2) Cos ? = 0,7 |
||
Direct current load in resistive mode (DC12) |
Voltage |
24 VDC |
48 VDC |
|||
Power |
24 W(2) |
24 W(4) |
||||
Direct current load in inductive mode (DC13) |
Voltage |
24 VDC |
48 VDC |
|||
Power (L/R = 7 ms) |
3 W(1) 10 W(2) |
3 W(1) 10 W(2) |
||||
Power (L/R = 20 ms) |
24 W(3) |
24 W(3) |
||||
Response time |
Activation |
< 8 ms |
||||
Deactivation |
< 10 ms |
|||||
On-line module change |
Possible |
|||||
Built-in protection |
Against alternating current inductive over voltage |
None. Fit an RC circuit or a ZNO type over voltage limiter in parallel on each output appropriate to the voltage in use. |
||||
Against direct current inductive over voltage |
None. Fit a discharge diode on each output. |
|||||
Against short-circuits and overloads |
None. Fit a fast-blow fuse of 12 A for each 8-channel group. |
|||||
Maximum switching frequency |
3 600 cycles per hour |
|||||
Power dissipation |
3 W max |
|||||
Dielectric strength (at 50/60 Hz for 1 min.) |
2000 V actual |
|||||
Resistance of insulation (at 500 VDC) |
> 10 MΩ |
|||||
Noise immunity |
In noise simulation below 1500 V actual, noise width of 1s and frequency of 25 to 60 Hz |
|||||
Reliability |
MTBF for continuous operation in hours at ambient temperature 30°C (86°F) |
1 357 810 |
||||
Power supply consumption |
3.3 V |
Typical |
79 mA |
|||
Maximum |
111 mA |
|||||
24 V relay(5) |
Typical |
89 mA |
||||
Maximum |
100 mA |
|||||
(1): 3 x 105 cycles, (2): 1 x 105 cycles, (3): 7 x 103 cycles, (4): 5 x 104 cycles, (5): per channel at 1. |