Altitude Operating Conditions
The characteristics in the table below apply to the modules BMX DRA 0805 and BMX DRA 0805H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
This table presents the general characteristics for the BMX DRA 0805 and BMX DRA 0805H modules:
Module type |
Relay outputs for alternating and direct current |
|||||
Operating temperature |
BMX DRA 0805 |
0...60 ºC (32...140 ºF) |
||||
BMX DRA 0805H |
-25...70 ºC (-13...158 ºF) |
|||||
Rated voltage |
Direct |
24 VDC |
||||
Alternating |
24...240 VAC |
|||||
Voltage range |
Direct |
10...34 VDC |
||||
Alternating |
19...264 VAC (47...63 Hz) |
|||||
Thermal current |
3 A |
|||||
Minimum switching load |
5 VDC / 10 mA |
|||||
Alternating current load in resistive mode (AC12) |
Voltage |
24 VAC |
48 VAC |
100...120 VAC |
200...240 VAC |
|
Power |
50 VA(5) |
50 VA(6) 110 VA(4) |
110 VA(6) 220 VA(4) |
220 VA(6) |
||
Maximum Power of Hardened module at 70°C (158°F) |
30 VA(5) |
30 VA(6) 66 VA(4) |
66 VA(6) 132 VA(4) |
132 VA(6) |
||
Alternating current load in inductive mode (AC15) |
Voltage |
24 VAC |
48 VAC |
100...120 VAC |
200...240 VAC |
|
Power |
24 VA(4) |
10 VA(10) 24 VA(8) |
10 VA(11) 50 VA(7) 110 VA(2) |
10 VA(11) 50 VA(9) 110 VA(6) 220 VA(1) |
||
Maximum Power of Hardened module at 70°C (158°F) |
14.4 VA(4) |
6 VA(10) 14.4 VA(8) |
6 VA(11) 30 VA(7) 66 VA(2) |
6 VA(11) 30 VA(9) 66 VA(6) 132 VA(1) |
||
Direct current load in resistive mode (DC12) |
Voltage |
24 VDC |
||||
Power |
24 W(6) 40 W(3) |
|||||
Maximum Power of Hardened module at 70°C (158°F) |
14.4 W(6) 24 W(3) |
|||||
Direct current load in inductive mode (DC13) (L:R=60 ms) |
Voltage |
24 VDC |
||||
Power |
10 W(8) 24 W(6) |
|||||
Maximum Power of Hardened module at 70°C (158°F) |
6 W(8) 14.4 W(6) |
|||||
Response time |
Activation |
< 10 ms |
||||
Deactivation |
< 8 ms |
|||||
Built-in protection |
Against inductive over voltage in AC modes |
None. Fit an RC circuit or a ZNO type over voltage limiter in parallel on each output appropriate to the voltage in use. |
||||
Against inductive over voltage in DC modes |
None. Fit a discharge diode on each output. |
|||||
against short-circuits and overloads |
None. Fit a fast-blow fuse of 3 A for each relay. |
|||||
Reliability |
MTBF for continuous operation in hours at ambient temperature 30°C (86°F) |
2 119 902 |
||||
Power dissipation |
2.7 W max. |
|||||
Dielectric strength (at 50/60 Hz for 1 min.) |
2000 V actual |
|||||
Resistance of insulation (at 500 VDC) |
>10 MΩ |
|||||
Power supply consumption |
3.3 V |
Typical |
79 mA |
|||
Maximum |
111 mA |
|||||
24 V relay(12) |
Typical |
51 mA |
||||
Maximum |
56 mA |
|||||
(1):0.1 x 106 cycles, (2): 0.15 x 106 cycles, (3): 0.3 x 106 cycles, (4): 0.5 x 106 cycles, (5): 0.7 x 106 cycles, (6): 1 x 106 cycles, (7): 1.5 x 106 cycles, (8): 2 x 106 cycles, (9): 3 x 106 cycles, (10): 5 x 106 cycles, (11): 10 x 106 cycles, (12): all channels at 1. |