Altitude Operating Conditions
The characteristics in the table below apply to the modules BMX DDO 6402 K and BMX DDO 6402 KC for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
This table presents the general characteristics for the BMX DDO 6402 K and BMX DDO 6402 KC modules:
Module type |
24 VDC positive logic static outputs |
||
Operating temperature |
0...60 ºC (32...140 ºF) |
||
Temperature derating |
Apply the temperature derating curve |
||
Nominal values |
Voltage |
24 VDC |
|
Current |
0.1 A |
||
Threshold values |
Voltage (including ripple) |
19...30 V (34 V possible for 1 hour/day) |
|
Current/channel |
0.125 A |
||
Current/module |
6.4 A |
||
Power of tungsten filament lamp |
Maximum |
1.2 W |
|
Leakage current |
At 0 |
100 μA for U = 30 V |
|
Voltage drop |
At 1 |
< 1.5 V for I = 0.1 A |
|
Load impedance |
Minimum |
220 Ω |
|
Response time(1) |
1.2 ms |
||
Max. overload time before internal damage |
15 ms |
||
Reliability |
MTBF for continuous operation in hours at ambient temperature 30 °C (86 °F) |
159 924 |
|
Frequency of switching to inductive load |
0.5 / LI2 Hz |
||
Paralleling of outputs |
Yes (maximum of 3) |
||
Compatibility with IEC 61131-2 DC direct inputs |
Yes (type 3 and no type) |
||
Built-in protection |
Against over voltage |
Yes, by Transil diode |
|
Against inversions |
Yes, by inverted diode(2) |
||
Against short-circuits and overloads |
Yes, by current limiter and electric circuit-breaker 0.125 A < Id < 0.185 A |
||
Fuse type |
Internal |
None |
|
External |
1 fast blow fuse of 2 A for each 16-channel group |
||
Pre-actuator voltage: monitoring threshold |
OK |
> 18 V |
|
Error |
< 14 V |
||
Pre-actuator voltage: monitoring response time |
On appearance |
8 ms < T < 30 ms |
|
On disappearance |
1 ms < T < 3 ms |
||
Power consumption 3.3 V |
Typical |
160 mA |
|
Maximum |
226 mA |
||
24 V pre-actuator consumption (excluding load current) |
Typical |
92 mA |
|
Maximum |
127 mA |
||
Power dissipation |
6.85 W max. |
||
Dielectric strength |
Output / ground or output / internal logic |
1500 V actual, 50 / 60 Hz for 1 min |
|
Between channel groups |
500 VDC |
||
Resistance of insulation |
>10 MΩ (below 500 VDC) |
||
(1) All outputs are equipped with fast demagnetization circuits for electromagnet. Electromagnet discharge time < L/R. (2) Provide a 2 A fuse to the +24 V pre-actuator supply. |