At a Glance
This is an overview of the sensor connections on TELEFAST 2 bases.
NOTE: The bases are manufactured with a general-purpose, quick-blow
fuse rated 2 A. To guarantee optimum protection, this fuse should
be rated according to the application and the maximum current allowable
in the base.
Type and rating of fuse to be fitted to the base:
input functions: 0.5A quick-blow
Illustration
Description of the connection terminal blocks.

Illustration
Input function connections.

Connecting the common for sensors:
to create the shared sensor supply:
position the jumper wire (1) on terminals 1 and 2: terminal blocks 200 to 215 will be at the "+" of the supply
link terminal 4 to one of the C terminals of the 3rd level (2): terminal blocks 300 to 315 will be at the "-" of the supply
NOTE: The ABE-7H16R30/R31 base can also be used for
connecting actuators.