Details of the IODDT's explicit exchange objects of type T_COUNT_ACQ
(Original Document)
At a Glance
This part shows the IODDT's implicit exchange objects of type T_COUNT_ACQ which applies to the three modules TSX CTY 2A/4A/2C. It brings together word-type objects whose bits have a special meaning. This objects are described in detail below.
Example of declaration of a variable: IODDT_VAR1 of type T_COUNT_ACQ
Notes
Explicit exchange operation indicators: EXCH_STS
The table below shows the meanings of exchange control bits of the channel EXCH_STS (%MWr.m.c.0).
Standard symbol
Type
Access
Meaning
Address
STS_IN_PROGR
BOOL
R
Reading channel status words
%MWr.m.c.0.0
ADJ_IN_PROGR
BOOL
R
Adjust parameters exchange in progress
%MWr.m.c.0.2
RECONF_IN_PROGR
BOOL
R
Reconfiguring of the module
%MWr.m.c.0.15
Explicit exchange report: EXCH_RPT
The table below shows the meanings of report bits EXCH_RPT (%MWr.m.c.1).
Standard symbol
Type
Access
Meaning
Address
STS_ERR
BOOL
R
Reading fault of channel state words
%MWr.m.c.1.0
ADJ_ERR
BOOL
R
Fault when exchanging adjustment parameters
%MWr.m.c.1.2
RECONF_ERR
BOOL
R
Fault when reconfiguring the channel
%MWr.m.c.1.15
Standard channel faults, CH_FLT
The table below shows the meanings of status word bits CH_FLT (%MWr.m.c.2). The reading is made by a READ_STS (IODDT_VAR1).
Standard symbol
Type
Access
Meaning
Address
COUNT_INP_FLT
BOOL
R
Counting input error
%MWr.m.c.2.0
COUNT_APP_FLT
BOOL
R
Counting application fault
%MWr.m.c.2.1
AUX_IO_FLT
BOOL
R
Auxiliary I/O fault
%MWr.m.c.2.3
INTERNAL_FLT
BOOL
R
Internal error or channel self-testing
%MWr.m.c.2.4
CONF_FLT
BOOL
R
Different hardware and software configurations
%MWr.m.c.2.5
COM_FLT
BOOL
R
Communication error with the PLC
%MWr.m.c.2.6
APPLI_FLT
BOOL
R
Application fault (adjustment or configuration fault)
%MWr.m.c.2.7
CH_LED0
BOOL
R
Green indicator’s command bits CHx (channel state)
00 = off, 01 = blinking, 11 = lit
%MWr.m.c.2.8
CH_LED1
BOOL
R
%MWr.m.c.2.9
AUX_PS_FLT
BOOL
R
Auxiliary I/O power supply fault
%MWr.m.c.2.11
SHORT_CIRCUIT
BOOL
R
Short-circuit fault on a channel
%MWr.m.c.2.12
ENC_PS_FLT
BOOL
R
Supply, encoder or potential difference error
%MWr.m.c.2.13
LINE_BRK_FLT
BOOL
R
Encoder line break or short-circuit error
%MWr.m.c.2.14
Specific channel faults, %MWr.m.c.3
The table below shows the meanings of channel status word bits %MWr.m.c.3. The reading is made by a READ_STS (IODDT_VAR1)
Standard symbol
Type
Access
Meaning
Address
CH_CONF_FLT
BOOL
R
Channel configuration error
%MWr.m.c.3.0
MEASURE_OVR
BOOL
R
Measurement overrun fault
%MWr.m.c.3.1
ABS_ENC_FLT
BOOL
R
Specific absolute encoder error
%MWr.m.c.3.2
Preset command, %MWr.m.c.4
The table below gives the meaning of the word PRESET (%MWr.m.c.4). The requests used are those associated with parameters (READ_PARAM,WRITE_PARAM..)
Standard symbol
Type
Access
Meaning
Address
PRESET
DINT
R/W
Preset value (parameter)
%MDr.m.c.4