Maintenance
(Original Document)
General
The TSX CTY 2A/4A/2C modules are fitted with LEDs on the front panel, which make it possible to view the state of the module and the counting channels:
Diagnostics
This table shows the diagnostics of the module according to the state of the LEDs:
Lit
Flashing
Off
RUN
Module operative
/
Module switched off or experiencing a fault
ERR
Internal module error:
module has broken down.
Communication error or awaiting configuration.
No error.
I/O
External module error:
  • wiring fault,
  • encoder supply error,
  • measurement overrun.
Application fault
/
No error.
CH
TSX CTY 2A/2C
CH0 and CH1
TSX CTY 4A
CH0, CH1, CH2, CH3.
The channel is operational.
The channel is not functioning correctly due to:
  • an internal fault,
  • an external fault,
  • a communication error,
  • an application fault.
Channel inoperative:
The channel is not configured, or is badly configured.
Illustration of module LEDs: