Modules
|
TSX CTY 2A
|
TSX CTY 4A
|
TSX CTY 2C
|
||
---|---|---|---|---|---|
Maximum frequency at the counter inputs
|
40 kHz
|
40 kHz
|
1 MHz
|
||
Current used by the module
|
5 V internal
|
Typical maximum
|
280 mA
330 mA
|
330 mA
470 mA
|
850mA (*)
1A (*)
|
24V sensors/pre-actuators
|
Typical maximum
|
30 mA
60 mA
|
36 mA
72 mA
|
15 mA
18 mA
|
|
Power dissipated in the module
|
Typical maximum
|
4.5 W
6 W
|
8 W
11.5 W
|
7 W
10 W
|
|
Sensor/pre-actuator supply monitoring
|
Yes
|
Yes
|
Yes
|
||
Operating temperature
|
0 to 60°C
|
0 to 60°C
|
0 to 60°C
|
||
Dielectric rigidity of inputs/ground or internal logic and inputs
|
1000 V efficient – 50/60 Hz/min
|
||||
Insulation resistance
|
> 10 MΩ under 500 VDC
|
||||
Hygrometry
|
5% to 95% without condensation.
|
||||
Storage temperature
|
-25° to +70°C
|
||||
Operating altitude
|
0 to 2000m
|