Standard symbol
|
Type
|
Access
|
Meaning
|
Language object
|
|---|---|---|---|---|
|
STS_IN_PROG
|
BOOL
|
R
|
Status parameter read in progress
|
%MWr.m.c.0.0
|
|
ADJ_IN_PROG
|
BOOL
|
R
|
Adjust parameter exchange in progress
|
%Mwr.m.c.0.2
|
|
RECONF_IN_PROG
|
BOOL
|
R
|
Reconfiguration in progress
|
%MWr.m.c.0.15
|
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Language object
|
|---|---|---|---|---|
|
STS_ERR
|
BOOL
|
R
|
Error while reading channel status
|
%MWr.m.c.1.0
|
|
ADJ_ERR
|
BOOL
|
R
|
Error while adjusting the channel
|
%Mwr.m.c.1.2
|
|
RECONF_ERR
|
BOOL
|
R
|
Error while reconfiguring the channel
|
%MWr.m.c.1.15
|
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Language object
|
|---|---|---|---|---|
|
EXTERNAL_FLT_INPUTS
|
BOOL
|
R
|
External error at inputs
|
%MWr.m.c.2.0
|
|
EXTERNAL_FLT_OUTPUTS
|
BOOL
|
R
|
External error at outputs
|
%MWr.m.c.2.1
|
|
INTERNAL_FLT
|
BOOL
|
R
|
Internal error: channel inoperative
|
%MWr.m.c.2.4
|
|
CONF_FLT
|
BOOL
|
R
|
Hardware or software configuration error
|
%MWr.m.c.2.5
|
|
COM_FLT
|
BOOL
|
R
|
Bus Communication error
|
%MWr.m.c.2.6
|
|
APPLI_FLT
|
BOOL
|
R
|
Application error
|
%MWr.m.c.2.7
|
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Language object
|
|---|---|---|---|---|
|
SENSOR_SUPPLY
|
BOOL
|
R
|
Low input power supply for the sensors
|
%MWr.m.c.3.2
|
|
ACTUATOR_SUPPLY_FLT
|
BOOL
|
R
|
Output power supply failure
|
%MWr.m.c.3.3
|
|
SHORT_CIRCUIT_OUT_0
|
BOOL
|
R
|
Short circuit on output 0
|
%MWr.m.c.3.4
|
|
SHORT_CIRCUIT_OUT_1
|
BOOL
|
R
|
Short circuit on output 1
|
%MWr.m.c.3.5
|