One Shot Counter Mode Configuration
Original instructions
At a Glance
The configuration of a counting module is stored in the configuration constants (%KW).
The parameters r,m and c shown in the following tables represent the topologic addressing of the module. Each parameter had the following signification:
Configuration Objects
The table below presents the one shot counter mode configurable elements
Label
Address in the configuration
Configurable values
Counting mode
%KWr.m.c.2
(least significant byte)
One shot counter mode. The value of the least significant byte of this word is 6.
IN_A input filter
%KWr.m.c.3
(least significant byte)
The least significant byte can take the following values:
  • 0: none,
  • 1: low,
  • 2: medium,
  • 3: high.
IN_SYNC input filter
%KWr.m.c.4
(least significant byte)
The least significant byte can take the following values:
  • 0: none,
  • 1: low,
  • 2: medium,
  • 3: high.
IN_EN input filter
%KWr.m.c.4
(most significant byte)
The most significant byte can take the following values:
  • 0: none,
  • 1: low,
  • 2: medium,
  • 3: high.
Input power supply fault
%KWr.m.c.2.8
General input/output fault (bit set to 0)
Local (bit set to 1)
Scale factor
%KWr.m.c.6
(least significant byte)
Edit (value in the range 1...255)
Synchronization edge
%KWr.m.c.10.8
Rising edge (bit set to 0)
Falling edge (bit set to 1)
Output block 0
%KWr.m.c.17
This word can take the following values:
  • 0: off,
  • 1: low counter,
  • 2: counter in a window,
  • 3: High counter,
  • 4: pulse = less than the lower threshold (LT),
  • 5: pulse = greater than the lower threshold (LT),
  • 6: pulse = less than the upper threshold (UT),
  • 7: pulse = greater than the upper threshold (UT).
Output block 1
%KWr.m.c.19
This word can take the following values:
  • 0: off,
  • 1: low counter,
  • 2: counter in a window,
  • 3: High counter,
  • 4: pulse = less than the lower threshold (LT),
  • 5: pulse = greater than the lower threshold (LT),
  • 6: pulse = less than the upper threshold (UT),
  • 7: pulse = greater than the upper threshold (UT).
Polarity 0
%KWr.m.c.21.1
Polarity + (bit set to 0)
Polarity - (bit set to 1)
Polarity 1
%KWr.m.c.21.2
Polarity + (bit set to 0)
Polarity - (bit set to 1)
Fault recovery
%KWr.m.c.21.0
Automatic reaction (bit set to 1)
Activated (bit set to 0)
Fallback 0
%KWr.m.c.21.3
None (bit set to 0)
With (bit set to 1)
Fallback 1
%KWr.m.c.21.4
None (bit set to 0)
With (bit set to 1)
Fallback value 0
%KWr.m.c.21.5
0 (bit set to 0)
1 (bit set to 1)
Fallback value 1
%KWr.m.c.21.6
0 (bit set to 0)
1 (bit set to 1)
Output power supply fault
%KWr.m.c.2.9
General input/output fault (bit set to 0)
Offline (bit set to 1)
Pulse width 0
%KWr.m.c.18
Edit (value in the range 1...65535)
Pulse width 1
%KWr.m.c.20
Edit (value in the range 1...65535)
Event
Event number
%KWr.m.c.0
Activated (if activated is selected, the entered event number is coded on the most significant byte of this word)
Deactivated (all bits of the most significant byte of this word are set to 1)