Module type
|
2 counting channels
|
||
|
Operating temperature
|
BMX EHC 0200
|
0...60 ºC (32...140 ºF)
|
|
|
BMX EHC 0200H
|
-25...70 ºC (-13...158 ºF)
|
||
|
Maximum frequency at counting inputs
|
60 kHz
|
||
|
Number of inputs/outputs per counting channel
|
Inputs
|
6 Type three 24 VDC inputs
|
|
|
Outputs
|
Two 24 VDC outputs
|
||
|
Power Supply
|
Sensor supply voltage
|
19.2...30 VDC
|
|
|
Module consumption
|
Does not take into account sensors or encoder consumption
|
||
|
Actuator supply current
|
500 mA maximum per output
2 A per module
|
||
|
Power distribution to sensors
|
Yes with short-circuit and overload protection - typical 300 mA (short-circuit limited to 2.5 A)
|
||
|
Hot replacement
|
Yes, under the following conditions:
The module may be removed and reinserted into its location while the rack is switched on, but the counter may have to be revalidated when it is reinserted into its base.
|
||
|
Dimensions
|
Width
|
Module only
|
32 mm
|
|
On the rack
|
32 mm
|
||
|
Height
|
Module only
|
103.76 mm
|
|
|
On the rack
|
103.76 mm
|
||
|
Depth
|
Module only
|
92 mm
|
|
|
On the rack
|
104.5 mm
|
||
|
Encoder compliance
|
10...30 VDC incremental encoder model with push-pull at outputs
|
||
|
Insulation voltage of the ground to the bus
|
1500 V RMS for 1 min
|
||
|
Rack 24 V supply bus
|
Current for the 24 V bus
|
Typical: 40 mA
|
|
|
Rack 3 V supply bus
|
Current for the 3 V bus
|
Typical: 200 mA
|
|
|
Module Cycle Time
|
1 ms
|
||
WARNING |
|
OVERHEATING MODULE
Do not operate the BMX EHC 0200H at 70°C (158°F) if the sensor power supply is greater than 26.4 V or less than 21.1 V.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
|
Number of inputs per channel
|
Six 24 VDC inputs
|
||
|
Inputs:
IN A, IN B, IN SYNC, IN EN, IN REF, IN CAP
|
Voltage
|
30 VDC maximum
|
|
|
At state 1
|
Voltage
|
11 VDC... 30 VDC
|
|
|
Current
|
5 mA (up to 30 VDC)
|
||
|
At state 0
|
Voltage
|
< 5 VDC
|
|
|
Current
|
< 1.5 mA
|
||
|
Current at 11 VDC
|
> 2 mA
|
||
|
Number of outputs per channel
|
2
|
|
|
Type
|
source 24 VDC 0.5 A
|
|
|
Voltage
|
19.2...30 VCC
|
|
|
Minimum load current
|
None
|
|
|
Maximum load current
|
Each point
|
0.5 A
|
|
Per module
|
2 A
|
|
|
Leakage current at state 0
|
0.1 mA maximum
|
|
|
Voltage drop at state 1
|
3 VDC maximum
|
|
|
Output current short-circuit
|
Each point
|
1.5 A maximum
|
|
Maximum load capacity
|
50 μF
|
|
|
Short-circuit and overload
|
Channel protection
|
|
|
Polarity for each output channel
|
By default
|
Normal logic on both channels
|
|
User configuration
|
Reverse logic for one or several channels
|
|
|
Maximum inductive load
|
The inductive load is calculated using the following formula:
![]() The formula above uses the following parameters:
|
|