Operating conditions
(Original Document)
Operating temperature
Hygrometry
Altitude
Mechanical standards
Electrostatic discharge standard
NOTE: Minimum level in conditions defined by the standards
HF interference standard
NOTE: Minimum level in conditions defined by the standards
LF interference standard
Premium PLC protection processing
Premium PLCs meet "ACP" (All Climate Processing) processing requirements.
For installations in industrial production workshops, or in an environment corresponding to "PWH" (Processing for Warm and Humid environments), Premium PLCs must be inserted into IP54 minimum protection envelopes as prescribed by IEC 664 and NFC 20 040 standards.
Reminder
Premium PLCs have an IP20 protection rating. They can therefore be installed without an envelope in premises with restricted access which do not exceed pollution level 2 (control room with no machines or dust-producing activity).
NOTE: When a position is not occupied by a module, a TSX RKA 02 protection cover must be installed in it.
Requirements relating to transport and storage
These requirements comply with the IEC 1131-2 standard.