Designation
|
Size
|
Description
|
---|---|---|
Total length
|
word
|
total length of configuration information
|
%IW number
|
byte
|
total input data size in the %IW zone
|
%QW number
|
byte
|
total output data size in the %QW zone
|
Offset %IW
|
word
|
input data blocks offset in the %IW zone
|
Offset %QW
|
word
|
input data blocks offset in the %QW zone
|
Station Status
|
byte
|
refer to the Profibus DP standard
|
Watchdog Factor 1
|
byte
|
|
Watchdog Factor 2
|
byte
|
|
Min TSDR
|
byte
|
|
PNO_IDENTIFIER
|
word
|
|
Group Flags
|
byte
|
|
ID Address
|
byte
|
slave address on the bus
|
Modular slave
|
byte
|
value = 1 if the slave is a modular device value = 0 if the slave is a compact device
|
Slave active
|
byte
|
value = 1 if slave is active on the bus
value = 0 if slave is inactive on the bus
|
Size of parameters
|
word
|
parameter data block size for this slave
|
Configuration data size
|
word
|
configuration data block size for this slave
|
Size of data used
|
word
|
data used block size for this slave
|
Parameters
|
x bytes
|
parameter data block for this slave
|
Configuration data
|
x bytes
|
configuration data block for this slave
|
Data used
|
x bytes
|
block of data used for this slave
|