Function mode of the WRITE_REG
block
Although a large number of WRITE_REG
function blocks can be programmed, only four write operations may
be active at the same time. In such a case it is insignificant whether
they are the result of this function block or others (e.g. MBP_MSTR
, CWRITE_REG
). All function blocks
use one data transaction path and require multiple cycles to complete
a job.
If several WRITE_REG
function blocks
are used within an application, they must at least differ in the values
of their NO_REG
or REG_WRIT
parameters.
The status signals DONE
and ERROR
report the function block state to the
user program.
All routing information is contained in the WordArr5
data structure of the ADDRFLD
input.
The type function block assigned to this input is defined by the network
used.
Please use:
Modbus Plus for function block
ModbusP_ADDR
TCP/IP Ethernet for function block
TCP_IP_ADDR
SY/MAX Ethernet for function block
SYMAX_IP_ADDR
WordArr5
data structure
can also be used with constants.