Starting the Application
(Original Document)
At a Glance
In this example, standard mode working requires the use of two PLCs, a discrete input module, a BMX NOM 0200 module, and 2 SR2MOD01 modems.
First Slave PLC Wiring
The first slave PLC is connected as following:
In this example, the first modem is connected to the processor serial port of the first slave PLC.
The actuator state controls the Start variable state in the application.
Second Slave PLC Wiring
The second slave PLC is connected as following:
In this example, the second modem is connected to the channel 0 of the BMX NOM 0200 module of the second slave PLC.
For a better communication reliability, the cable TCS XCN 3M4F3S4 is used for DTR/DSR/DCD modem signals handling by the application.
Configuration of the Second Slave PLC
Before transferring the project for configuring the second slave PLC, verify that the second slave PLC is not connected to the modem.
The table below shows the procedure for transfering the project in standard mode:
Step
Action
1
In the PLC menu, click on Standard Mode,
2
In the Build menu, click on Rebuild All Project. Your project is generated and is ready to be transferred to the PLC.
3
In the PLC menu, click on Connect. You are now connected to the PLC.
4
In the PLC menu, click on Transfer Project to PLC. The Transfer Project to PLC window opens. Click on Transfer. The application is transferred to the PLC.
5
Connect the second slave PLC to a SR2MOD01 modem.
Application Transfer to the First Slave PLC
Before transferring the application, verify that the first slave PLC is not connected to the modem.
The table below shows the procedure for transfering the application in standard mode:
Step
Action
1
In the PLC menu, click on Standard Mode,
2
In the Build menu, click on Rebuild All Project. Your project is generated and is ready to be transferred to the PLC. When you generate the project, you will see a results window. If there is an error in the program, Control Expert indicates its location (click on the highlighted sequence).
3
In the PLC menu, click on Connect. You are now connected to the PLC.
4
In the PLC menu, click on Transfer Project to PLC. The Transfer Project to PLC window opens. Click on Transfer. The application is transferred to the PLC.
Application Execution on the First Slave PLC
The table below shows the procedure for executing the application in standard mode:
Step
Action
1
In the PLC, click on Run. The Run window opens. Click on OK. The application is now being executed on the PLC.
2
Disconnect the PC which is running Control Expert software from the first slave PLC.
3
Connect the first slave PLC to a SR2MOD01 modem.