This type of communication is available for Premium PLCs via:
The maximum frame size is 256 bytes.
The PCMCIA cards and the built-in link of the TSX SCY 11601/21601 can process 8 communication functions simultaneously in Modbus master.
The READ_VAR communication function can read up to 1000 consecutive bits in any remote device. To read in excess of 1000 bits, the SEND_REQ communication function must be used.
NOTE: Premium PLCs cannot send over 1000 bits following a read request.
NOTE: Be careful that two masters (on the same bus) do not send requests simultaneously otherwise the requests are lost and each report will have a bad result which could be 16#0100 (request could not be processed) or 16#ODFF (slave is not present).