This type of communication is available for Premium PLCs:
-
Via the terminal port associated with the RS485 physical layer
-
Via the host channel of the processor or TSX SCY 21601 module with:
-
a TSX SCP 111 PCMCIA card associated with the RS232 physical layer
-
a TSX SCP 112 PCMCIA card associated with 20 mA current loops
-
a TSX SCP 114 PCMCIA card associated with physical layers RS422 and RS485
-
Via the built-in link of the TSX SCY 21601 module associated with the RS485 physical layer
The terminal port of Premium processors allows processing:
For communication via a Terminal port, the maximum frame size is 128 bytes per communication function.
PCMCIA cards and the link built into TSX SCY 21601 modules authorizes processing of:
For communication via a PCMCIA card or built in link, the maximum frame size is 210 bytes per communication function.
The READ_VAR communication function can read up to 1000 consecutive bits in any remote device. To read in excess of 1000 bits, the SEND_REQ communication function must be used.
NOTE: Premium PLCs cannot send over 1000 bits following a read request.