Details of IODDT Implicit exchange objects of type T_COM_IBS_242 for the modules TSX IBY 100 and TSX IBX 100
|
|
(Original Document)
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
CH_ERROR
|
EBOOL
|
R
|
Communication channel error bit.
|
%Ir.m.c.ERR
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
IBS_FLT
|
BOOL
|
R
|
bit 0 = 1: if bit 8 = 1 or bit 9 = 1 or bit 10 = 1.
|
%IWr.m.0.242.0
|
INTERNAL_FLT
|
BOOL
|
R
|
bit 4 = 1: internal fault (Module out of order).
|
%IWr.m.0.242.4
|
SOFT_CONF
|
BOOL
|
R
|
bit 7 = 1: incorrect software configuration.
|
%IWr.m.0.242.7
|
MAST_OFF
|
BOOL
|
R
|
bit 8 = 1: INTERBUS master not operating.
|
%IWr.m.0.242.8
|
DP_EXCH_FLT
|
BOOL
|
R
|
bit 9 = 1: DP exchange fault.
|
%IWr.m.0.242.9
|
PMS_EXCH_FLT
|
BOOL
|
R
|
bit 10 = 1: PMS message handling exchange fault.
|
%IWr.m.0.242.10
|
OUTP_FLT
|
BOOL
|
R
|
bit 11 = 1: output in fallback mode on a bus stop.
|
%IWr.m.0.242.11
|
CONF_FLT
|
BOOL
|
R
|
bit 13 = 1: module configuration fault.
|
%IWr.m.0.242.13
|
COM_FLT
|
BOOL
|
R
|
bit 14 = 1: problem communicating with the PLC.
|
%IWr.m.0.242.14
|
MSG_ERR
|
BOOL
|
R
|
bit 15 = 1: reception of an error message.
|
%IWr.m.0.242.15
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
PAR_SEG_NBR_ERR
|
INT
|
R
|
This word designates an error code referenced in the Phoenix Contact documentation, %IWr.m.0.244.0 or .3 = 1 or
the number of the faulty bus segment, if %IWr.m.0.244.1 or.2 = 1.
|
%IWr.m.0.243
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
USR_PAR_ERR
|
BOOL
|
R
|
bit 0 = 1: user fault (usr), %IWr.m.0.243 refers to the error code referenced in the Phoenix Contact documentation.
|
%IWr.m.0.244.0
|
PERIPH_ERR
|
BOOL
|
R
|
bit 1 = 1: Peripheral fault (pf), location of fault by %IWr.m.0.243.
|
%IWr.m.0.244.1
|
BUS_ERR
|
BOOL
|
R
|
bit 2 = 1: fault on local bus, installation Remote bus or remote bus (bus), location of fault by %IWr.m.0.243.
|
%IWr.m.0.244.2
|
CTRL_ERR
|
BOOL
|
R
|
bit 3 = 1: controller fault (ctrl), %IWr.m.0.243 refers to the error code referenced in the Phoenix Contact documentation.
|
%IWr.m.0.244.3
|
OP_DETECT_FLT
|
BOOL
|
R
|
bit 4 = 1: operation detection error (dtct).
|
%IWr.m.0.244.4
|
DATA_EXCH
|
BOOL
|
R
|
bit 5 = 1: IBS cyclic exchange (run).
|
%IWr.m.0.244.5
|
BUS_ACTIV
|
BOOL
|
R
|
bit 6 = 1: IBS active: identification cycles (act).
|
%IWr.m.0.244.6
|
CTRL_RDY
|
BOOL
|
R
|
bit 7 = 1: IBS ready for configuration (rdy).
|
%IWr.m.0.244.7
|
BUS_INACTIV
|
BOOL
|
R
|
bit 8 = 1: at least one segment of bus deactivated (bsa).
|
%IWr.m.0.244.8
|
HOST_FLT
|
BOOL
|
R
|
bit 9 = 1: Host error (fail).
|
%IWr.m.0.244.9
|
FCT_RES_NEG
|
BOOL
|
R
|
command execution (r) tested using the register %QWr.m.c.248,
bit 10 = 0 the command has been executed.
|
%IWr.m.0.244.10
|
SYNC_ERR
|
BOOL
|
R
|
bit 11 = 1: synchronization fault only synchronized mode operating (syr).
|
%IWr.m.0.244.11
|
DATA_CYCL_ERR
|
BOOL
|
R
|
bit 12 = 1: data cycle error only synchronized code operating (dcr).
|
%IWr.m.0.244.12
|
SCAN_TIME_OVR
|
BOOL
|
R
|
bit 13 = 1: cycle time overflow (w).
|
%IWr.m.0.244.13
|
BAD_BUS_QUAL
|
BOOL
|
R
|
bit 14 = 1: bad bus quality (q).
|
%IWr.m.0.244.14
|
SLAVE_RDY
|
BOOL
|
R
|
bit 15 = 1: message on standby in standard interface (ssi).
|
%IWr.m.0.244.15
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
MASTER_FLT
|
BOOL
|
R
|
bit 8 = 1: master fault.
|
%IWr.m.0.245.8
|
MAST_RDY
|
BOOL
|
R
|
bit 11 = 1: master ready to communicate.
|
%IWr.m.0.245.11
|
MOD_FLT
|
BOOL
|
R
|
bit 12 = 1: TSX IBY / IBX 100 module fault.
|
%IWr.m.0.245.12
|
MOD_RDY_COM
|
BOOL
|
R
|
bit 15 = 1: TSX IBY / IBX 100 module ready to communicate.
|
%IWr.m.0.245.15
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
SCAN_TIME_LSB
|
INT
|
R
|
IBS scan time (s): D-Word (least significant)
|
%IWr.m.0.246
|
SCAN_TIME_MSB
|
INT
|
R
|
IBS scan time (s): D-Word (most significant)
|
%IWr.m.0.247
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
IBS_CTRL
|
INT
|
R
|
Image of IBS commands. IBS confirms receipt of the command by resetting the bit %IWr.m.0.248.i to 1, corresponding to the command %QWr.m.0.248.i.
|
%IWr.m.0.248
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
OUT_IN_NBR
|
INT
|
R
|
This word designates the exchange number %QW and %IW.
|
%IWr.m.0.249
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
DP_EXCH_FLT_W
|
INT
|
R
|
DP exchange fault code (equal to 0: OK, not equal to 0: internal fault).
|
%IWr.m.0.250
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
MSG_NBR_RCV
|
INT
|
R
|
Number of PMS messages received.
|
%IWr.m.0.251
|
MSG_NBR_SENT
|
INT
|
R
|
Number of PMS messages sent.
|
%IWr.m.0.252
|
MSG_FLT
|
INT
|
R
|
DP exchange fault code.
(equal to 0: OK; not equal to 0: internal fault).
|
%IWr.m.0.253
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
AUTO_START
|
BOOL
|
R/W
|
bit 0 = 1: automatic start-up after IBS disappearance of a fault.
|
%QWr.m.0.242.0
|
STOP_PROC
|
BOOL
|
R/W
|
bit 1 = 1: preprocessing stopped upon application stop and outputs change to configured state in STOP mode (Fallback mode or Maintenance).
|
%QWr.m.0.242.1
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
SYS_START
|
BOOL
|
R/W
|
bit 0 = 1: launch of the INTERBUS (2) system (Start Bus).
|
%QWr.m.0.248.0
|
SYS_STOP
|
BOOL
|
R/W
|
bit 1 = 1: stop of INTERBUS system (Stop Bus), reset outputs, reconfiguration (3).
|
%QWr.m.0.248.1
|
ACK_FLT
|
BOOL
|
R/W
|
bit 2 = 1: acknowledgement of fault %IWr.m.0.244.
|
%QWr.m.0.248.2
|
DESACT_EQMT
|
BOOL
|
R/W
|
bit 3 = 1: deactivation of a device (3).
|
%QWr.m.0.248.3
|
ACTIV_EQMT
|
BOOL
|
R/W
|
bit 4 = 1: activation of a device (3).
|
%QWr.m.0.248.4
|
SHUNT_EQMT
|
BOOL
|
R/W
|
bit 5 = 1: device shunt (3) (4).
|
%QWr.m.0.248.5
|
REVERS_EQMT
|
BOOL
|
R/W
|
bit 6 = 1: removal of a shunt (3).
|
%QWr.m.0.248.6
|
Key
|
||||
(2)
|
Important
If this bit is not reset, the INTERBUS bus restarts automatically once a fault has disappeared.
|
|||
(3)
|
For this service, the parameters of %QWr.m.0.249 are necessary
|
|||
(4)
|
This command is valid only if the bus is inactive. After executing the command, the device should be disconnected from the bus before restarting the INTERBUS.
|
Standard symbol
|
Type
|
Access
|
Meaning
|
Address
|
---|---|---|---|---|
ELMT_NBR
|
INT
|
R/W
|
This word designates the number of the current configuration (value 1), if %QWm.0.248.1 = 1.
This word designates the number of the device concerned (segment.position), if %QWm.0.248.1 at bit 6 = 1.
|
%QWr.m.0.249
|