Type of fault
|
Causes of fault
|
Corrective action
|
---|---|---|
BUS LED on
|
Network cable disconnected: various causes (physical fault)
|
|
24 V module power supply cut-off: various causes
|
|
|
Functions not carried out by the communication interfaces of the TSX IBY 100 and IBX 100 modules: elementary failure or faulty interface connection
|
|
|
INTERBUS slave module declared but not present on the bus: programming error
|
|
|
INTERBUS slave module not declared but present on the bus: programming error
|
||
Incorrect reference declared for the slave module in the software configuration: programming error
|
||
Elementary failure of the slave device
|
|
|
Functions not carried out by the communication interfaces of a slave: elementary failure or faulty interface connection (physical fault)
|
||
PF LED on
|
24 V power supply to module sensors cut-off: various causes
|
|
24 V actuator power supply cut off: various causes
|
|
|
Sensor I/O short-circuit: various causes
|
|
|
Sensor input/power supply short-circuit: various causes
|
|
|
QUAL LED on
|
Caused by electromagnetic interference on the slave device
|
|
Fallback outputs (maintained or reset)
|
PLC in STOP position
|
|
Outputs reset to "0"
|
Application not present in PLC:
|
|
Elementary failure of TSX IBY 100/IBX 100 module: various causes
|
|
|
Elementary failure of PLC power supply: various causes
|
|