For the TSX IBX 100 module, you need to use a TSX PCI 57 ••• type PLC.
The TSX PCI 57 204 processor can manage one TSX IBX 100 module.
The TSX PCI 57 354 processor (version of Unity Pro > 1.0) can manage three TSX IBX 100 modules.
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.
TSX IBX 100 modules can manage 510 slaves
To receive a TSX IBX 100 module, the PC must:
-
be running Windows XP/2000,
-
use a 16 bit ISA bus and an available slot,
-
have sufficient power at its disposal to supply the processor and the module.
TSX IBX 100 modules are compatible with CMD Tool software of version V4.41 or above. Application topology, debugging and diagnostics of the INTERBUS field bus can be performed with this software.
The following table presents the number of inputs/outputs words (%IW/%QW) exchanged in a PLC cycle according to the module version.
TSX IBX 100 version
|
Number of input/output words
|
Lower than V3.0
|
128 words
|
V3.0 or higher
|
242 words
|