The Fipio messaging service is used for communication between:
-
the bus arbiter and a Premium or Micro PLC agent (equipped with a TSX FPP 10 card) or between agents,
-
Control Expert and Fipio agents (Premium or Micro PLC),
-
the bus arbiter with devices such as the HMI terminal (XBT), variable speed controllers (Altivar) or Lexium drives.
If the messaging service is saturated, the system returns an increasing number of time-out errors. Start by increasing the bandwidth allocated to the messaging service. If the problem persists,
decrease the message rate.
This problem mainly occurs on TSX P57 554 processors which have a very short cycle time.