Details of the Language Objects for the IODDT of Type T_STDP_GEN
(Original Document)
At a Glance
The tables below present the objects for the T_STDP_GEN-type IODDT that are applicable to all Fipio standard profiles.
Error Bit %I\2.e\0.m.c.ERR
The table below presents the error bit %I\2.e\0.m.c.ERR..
Standard Symbol
Type
Access
Meaning
Address
CH_ERROR
BOOL
R
Channel c error bit
%I\2.e\0.m.c.ERR
Execution Indicators of an Explicit Exchange: EXCH_STS
The table below presents the meanings of the exchange control bits of the channel EXCH_STS (%MW\2.e\0.m.c.0).
Standard Symbol
Type
Access
Meaning
Address
STS_IN_PROGR
BOOL
R
Reading of channel status words in progress
%MW\2.e\0.m.c.0.0
CMD_IN_PROGR
BOOL
R
Current command parameters exchange in progress
%MW\2.e\0.m.c.0.1
ADJ_IN_PROGR
BOOL
R
Adjustment parameters exchange in progress
%MW\2.e\0.m.c.0.2
RECONF_IN_PROGR
BOOL
R
Reconfiguration in progress
%MW\2.e\0.m.c.0.15
Explicit Exchange Report: EXCH_RPT
The table below presents the meaning of the exchange report bits EXCH_RPT (%MW\2.e\0.m.c.1).
Standard Symbol
Type
Access
Meaning
Address
STS_ERR
BOOL
R
Reading error for channel status words
%MW\2.e\0.m.c.1.0
CMD_ERR
BOOL
R
Error during command parameter exchange
%MW\2.e\0.m.c.1.1
ADJ_ERR
BOOL
R
Error during adjustment parameters exchange
%MW\2.e\0.m.c.1.2
RECONF_ERR
BOOL
R
Error when configuring the channel
%MW\2.e\0..m.c.1.15
Standard Channel Faults, CH_FLT
The following table presents the meanings of the bits of the CH_FLT status word (%MW\2.e\0.m.c.2). The reading is performed by a READ_STS (IODDT_VAR1).
Standard Symbol
Type
Access
Meaning
Address
INTERNAL_FLT
BOOL
R
Internal error or channel self-testing
%MW\2.e\0.m.c.2.4
CONF_FLT
BOOL
R
Hardware or software configuration error
%MW\2.e\0.m.c.2.5
COM_FLT
BOOL
R
Bus communication fault
%MW\2.e\0.m.c.2.6
APPLI_FLT
BOOL
R
Application fault (adjustment or configuration error)
%MW\2.e\0.m.c.2.7