Structure
|
|
---|---|
Nature
|
Open field bus, conforming to World FIP and FIP standards.
|
Topology
|
Devices linked by chaining or branching.
|
Access method
|
Managed by a bus arbiter
|
Communication
|
By exchange of variables which can be accessed by the user in the form of Control Expert objects and X-Way datagrams.
|
Privileged exchanges
|
Cyclical exchange of status variables and remote input/output commands
|
Transmission
|
|
---|---|
Binary rate
|
1 Mb/s.
|
Medium
|
Shielded twisted pair (150 Ohms of characteristic impedance) or fiber optic.
|
Configuration
|
|
---|---|
Number of connection points
|
128 logic connection points for whole architecture
|
Number of segments
|
15 maximum (in cascade format) using electrical or optical repeaters (14 maximum in cascade format).
|
Number of repeaters
|
An electrical or optical repeater is required every 1000 meters or every 32 devices.
|
PLC
|
One manager PLC (connection point address 0).
|
Programming terminal
|
One programming terminal (must be connected to connection point 63).
|
Length
|
The length of a segment depends on its type of branches:
|
![]() |
UNEXPECTED EQUIPMENT OPERATION
You are advised against connecting/disconnecting elements from the Fipio bus while powered up as certain devices may then not restart.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|