Details of T_SAP10_STD-type IODDT Explicit Language Objects
(Original Document)
At a Glance
The tables below present the T_SAP10_STD-type IODDT explicit objects that are applicable to all Fipio standard profiles.
Execution Indicators of an Explicit Exchange: EXCH_STS
The table below presents the meanings of the exchange control bits of the channel EXCH_STS (%MW\2.e\0.m.c.0).
Standard symbol
Type
Access
Meaning
Address
STS_IN_PROGR
BOOL
R
Reading of channel status words in progress.
%MW\2.e\0.m.c.0.0
CMD_IN_PROGR
BOOL
R
Current command parameters exchange in progress.
%MW\2.e\0.m.c.0.1
ADJ_IN_PROGR
BOOL
R
Adjustment parameters exchange in progress.
%MW\2.e\0.m.c.0.2
RECONF_IN_PROGR
BOOL
R
Reconfiguration in progress.
%MW\2.e\0.m.c.0.15
Explicit Exchange Report: EXCH_RPT
The table below presents the meaning of the exchange report bits EXCH_RPT (%MW\2.e\0.m.c.1).
Standard symbol
Type
Access
Meaning
Address
STS_ERR
BOOL
R
Reading error for channel status words.
%MW\2.e\0.m.c.1.0
CMD_ERR
BOOL
R
Error during command parameter exchange.
%MW\2.e\0.m.c.1.1
ADJ_ERR
BOOL
R
Error during adjustment parameters exchange.
%MW\2.e\0.m.c.1.2
RECONF_ERR
BOOL
R
Error when configuring channel.
%MW\2.e\0.m.c.1.15
Standard Channel Faults, CH_FLT
The status word CH_FLT provides information on all slaves on the AS-i communication channel.
This 16-bit word contains diagnostics information for the TBX SAP 10 module and diagnostics information relating to exchanges with the TBX SAP 10 across the Fipio network.
The following table shows the meaning of the bits of the status word CH_FLT (%MW\2.e\0.m.c.2).
Standard symbol
Type
Access
Object
Meaning
Function
-
BOOL
R
%MW\2.e\0.m.c.2.0
bit 0: not used.
Statuses generated by the TBX SAP 10
ASI_CONF_FLT
BOOL
R
%MW\2.e\0.m.c.2.1
AS-i bus configuration fault.
SLAVE0_FLT
BOOL
R
%MW\2.e\0.m.c.2.2
slave present at address 0 on AS-i bus.
ASI_SUPPLY_FLT
BOOL
R
%MW\2.e\0.m.c.2.3
AS-i power supply missing.
INTERNAL_FLT
BOOL
R
%MW\2.e\0.m.c.2.4
internal module fault (failure).
CONF_FLT
BOOL
R
%MW\2.e\0.m.c.2.5
hardware configuration fault.
COM_FLT
BOOL
R
%MW\2.e\0.m.c.2.6
communication fault with PLC.
APPLI_FLT
BOOL
R
%MW\2.e\0.m.c.2.7
application fault.
PLC_CONF_FLT
BOOL
R
%MW\2.e\0.m.c.2.8
PLC configuration fault.
Statuses generated by the PLC
MOD_MISSING
BOOL
R
%MW\2.e\0.m.c.2.9
module missing.
MOD_NOT_OP
BOOL
R
%MW\2.e\0.m.c.2.10
module not operational.
MOD_FLT
BOOL
R
%MW\2.e\0.m.c.2.11
module fault.
PLC_HW_FLT
BOOL
R
%MW\2.e\0.m.c.2.12
internal fault, PLC hardware fault.
PLC_SYS_FLT
BOOL
R
%MW\2.e\0.m.c.2.13
internal fault, PLC system fault.
FIP_COM_FLT
BOOL
R
%MW\2.e\0.m.c.2.14
dialog fault, Fipio communication fault.
PRM_FLT
BOOL
R
%MW\2.e\0.m.c.2.15
dialog fault, TBX SAP 10 parameter error.
Slave Parameters, PRM SLV
The following table presents the language objects that contain the value of the parameters sent to the AS-i intelligent slaves using the TBX SAP 10 module.
Standard symbol
Type
Access
Meaning
Address
PRM_SLV_0 to PRM_SLV_31
INT
RW
Parameters of slave 0 to slave 31. Contains the reply (value of the parameters sent) from the last slave parameterized. This allows you to verify via Control Expert that the slave has received them correctly.
%MW\2.e\0.m.c.4 to %MW\2.e.\0.m.c.35