Managing Faulty Devices
Original instructions
Introduction
The objective of this service is to provide automatic recovery of remote I/O module parameters or intelligent modules connected to a Transparent Factory Ethernet sub-segment. When exchanging a faulty module with a functioning module.
Objective
The objective of this service is to:
Operation
This server requires the use of the DHCP server and the FTP/TFTP server of the TSX ETY 4103/PORT/5103 modules or the Ethernet link of the TSX P57 6634/5634/4634.
The following modules can configure up to 96 devices:
The following coprocessors can configure up to 128 devices:
Service operating principle:
Initially:
  1. The valid remote station obtains an IP address from the name that has been given to it (Role Name).
  2. The valid station gives its configuration parameters to the server.
Secondly:
This station breaks down. It is replaced with a non-configured device of the same type, which has the same name as the station it replaces:
  1. It then transmits a DHCP request to the server.
  2. It receives its configuration file, which was saved first on the server.
  3. The remote station restarts automatically.
NOTE: The Role Name is limited to 16 characters in ASCII.