Display Panel, Ethernet Diagnostics for TSX P57 6634/5634/4634 Processors
Original instructions
Display Block
The display block for the TSX P57 6634/5634/4634 processors complies with the Premium standard; it has two LEDs specific to the integrated Ethernet channel, the STS and ACT LEDs.
The dedicated Ethernet LEDs define:
Ethernet Channel Diagnostics
Meaning of the diagnostics LEDs:
I/O
STS
ACT
Meaning
O
O
O
No supply to module.
P
O
ns
Ethernet link not operational.
ns
F
ns
Module configured. Diagnostics according to how the LEDs are flashing:
  • Steady flashing: Ethernet link awaiting configuration or configuration in process.
  • 2 flashes: no MAC address.
  • 3 flashes: Ethernet cable not connected on the module or Hub side
  • 4 flashes: the IP address is duplicated by another IP address on the network. Module is set to its default IP address. Conflicting remote device flashing in the same way.
  • 5 flashes: the Ethernet channel is configured as a BOOTP client and is waiting for a BOOTP server response.
  • 6 flashes: Invalid IP address. Module is set to its default IP address.
  • 7 flashes: the version of the Ethernet firmware is incompatible with the PLC processor firmware version (in cases where there are updates and user downloads).
O
P
ns
Ethernet link configured, operational.
O
P
F
Ethernet communication sending/receiving.
P = Permanently on, F = flashing, O = Off, ns = not significant