Details of Implicit Exchange Objects of the IODDT of Type T_COM_ETY_1X0
Original instructions
Introduction
The IODDT of type T_COM_ETY_1X0 has implicit exchange objects, which are described below. This type of IODDT applies to the modules TSX ETY 110 and TSX ETY 120.
Example of declaring a variable: IODDT_VAR1 of type T_COM_ETY_1X0
Generally speaking, the meaning of bits is given for state 1 of this bit. In specific cases, the two states of the bit are explained.
List of Implicit Exchange Objects
WARNING
UNEXPECTED APPLICATION BEHAVIOR-VALIDITY OF COMMON WORDS
The update bit switches to 1 at the beginning of the PLC cycle if it receives common words from the corresponding station. At the end of the cycle the update bits automatically return to 0.
Consequently, common words can only be considered valid if the update bit of the corresponding station is set to 1.
After power up, common words are set to value 0.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The table below shows the implicit exchange objects of the IODDT of type T_COM_ETY_1X0 which applies to the two modules TSX ETY110/120.
Standard symbol
Type
Access
Meaning
Address
CH_ERROR
EBOOL
R
Line error bit.
%Ir.m.c.ERR
NET_STS
BOOL
R
Reception bit of common words of at least one of the remote stations
%Ir.m.c.0.0
REFRESH_ID_0
to
REFRESH_ID_15
BOOL
R
Indicates that the common words of the station 0 to 15 are refreshed
%Ir.m.c.1.0
to
%Ir.m.c.1.15
REFRESH_ID_16
to
REFRESH_ID_31
BOOL
R
Indicates that the common words of the station 16 to 31 are refreshed
%Ir.m.c.2.0
to
%Ir.m.c.2.15
REFRESH_ID_32
to
REFRESH_ID_47
BOOL
R
Indicates that the common words of the station 32 to 47 are refreshed
%Ir.m.c.3.0
to
%Ir.m.c.3.15
REFRESH_ID_48
to
REFRESH_ID_63
BOOL
R
Indicates that the common words of the station 48 to 63 are refreshed
%Ir.m.c.4.0
to
%Ir.m.c.4.15