Configuring the General Parameters for Global Data
Original instructions
At a Glance
The following parameters can be entered in the Global Data Configuration zone of the configuration screen:
Group Address
This zone is used to enter the multicast IP address (class D) for the group to which the station belongs. The value 239.255.255.255 is the default value.
Group Name
This field is used to fill in the group name associating a variable from the variable editor with a module.
Distribution Period
This zone is used to select the distribution period of the publication. The publication is synchronized with the PLC master task. The publication period can be configured from 1 scan to 50 scans.
Health Time Out
This zone is used to adjust the health "time-out" value.
An associated status bit (%IW zone) is linked to each Global Data item and is used to monitor whether the data has been published and received by the end of the time indicated in this window. If yes, the value is 1, otherwise the bit is set to 0.
Multicast Filtering
The multicast filtering drop down list allows you select the following:
Note: The following modules support IGMP V1:
This function is used to reduce data flow on large networks.