Depending on the configuration of the TSX ETY 110 module, you can carry out messaging:
-
on the ETHWAY profile
-
on the TCP/IP profile
When the module is the client, the ETHWAY or TCP/IP profile is fixed by the configuration of stations in the module’s connection table.
The following table specifies which profile is used according to the configuration of the table.
|
If the address of the remote station is …
|
referenced in the table
|
not referenced in the table
|
Communication profile
|
TCP/IP
|
ETHWAY
|
NOTE: If no station is recorded in the table, the communication profile is ETHWAY.
When the module is the server, the ETHWAY or TCP/IP profile is fixed according to the client device :
-
If the client transmits on the ETHWAY profile, the module responds on the ETHWAY profile.
-
If the client transmits on the TCP/IP profile, the module responds on the TCP/IP profile.
NOTE: Where access control is activated, compatibility must be ensured between the client and server’s connection tables. If the client’s address is referenced in the server’s table, the client must communicate on the TCP/IP profile.