Tables of Error Codes for the CONT_CTL Library
Original instructions
Introduction
The following tables show the error codes and error values created for the EFBs of the CONT_CTL Library.
Conditioning
Table of error codes and errors values created for EFBs of the Conditioning family.
EFB name
Error code
ENO state in case of error
Error value in Dec
Error value in Hex
Error description
DTIME
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
DTIME
FP_ERROR
F
-
-
DTIME
Status word values
T/F
-
-
For details about the DTIME status word refer to the DTIME desription
INTEGRATOR
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
INTEGRATOR
E_ERR_IB_MAX_MIN
F
-30102
16#8A6A
YMAX < YMIN
INTEGRATOR
FP_ERROR
F
-
-
LAG_FILTER
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
LAG_FILTER
FP_ERROR
F
-
-
LDLG
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
LDLG
FP_ERROR
F
-
-
LEAD
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
LEAD
FP_ERROR
F
-
-
MFLOW
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
MFLOW
FP_ERROR
F
-
-
MFLOW
Status word values
T/F
-
-
For details about the MFLOW status word refer to the MFLOW desription
QDTIME
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
SCALING
E_ERR_NULL_INPUT_SCALE
F
-30121
16#8A57
Null input scale: max and min limit must be different
SCALING
FP_ERROR
F
-
-
SCALING
Status word values
T/F
-
-
For details about the SCALING status word refer to the SCALING description
TOTALIZER
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
TOTALIZER
FP_ERROR
F
-
-
TOTALIZER
W_WARN_TOTALIZER_CTER_MAX
T
30113
16#75A1
Maximum value of cter has been reached
TOTALIZER
Status word values
T/F
-
-
For details about the TOTALIZER status word refer to the TOTALIZER description
VEL_LIM
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
VEL_LIM
E_ERR_AB1_MAX_MIN
F
-30101
16#8A6B
YMAX < YMIN
VEL_LIM
FP_ERROR
F
-
-
Controller
Table of error codes and errors values created for EFBs of the Controller family.
EFB name
Error code
ENO state in case of error
Error value in Dec
Error value in Hex
Error description
AUTOTUNE
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
AUTOTUNE
E_ERR_NULL_INPUT_SCALE
F
-30121
16#8A57
Null input scale: max and min limit must be different
AUTOTUNE
W_WARN_AUTOTUNE_FAILED
T
30111
16#759F
AUTOTUNE has failed
AUTOTUNE
FP_ERROR
F
-
-
AUTOTUNE
E_ERR_AUTOTUNE_ID_UNKNOWN
F
-30120
16#8A58
The tuned EFB is not allowed or has not yet been called
AUTOTUNE
Status word values
T/F
-
-
For details about the AUTOTUNE status word refer to the AUTOTUNE description
PI_B
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
PI_B
E_ERR_NULL_INPUT_SCALE
F
-30121
16#8A57
Null input scale: max and min limit must be different
PI_B
FP_ERROR
F
-
-
PI_B
Status word values
T/F
-
-
For details about the PI_B status word refer to the PI_B description
PIDFF
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
PIDFF
E_ERR_NULL_INPUT_SCALE
F
-30121
16#8A57
Null input scale: max and min limit must be different
PIDFF
FP_ERROR
F
-
-
PIDFF
Status word values
T/F
-
-
For details about the PIDFF status word refer to the PIDFF description
SAMPLETM
E_EFB_SAMPLE_TIME_OVERFLOW
F
-30184
16#8A18
Internal error
STEP2
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
STEP2
FP_ERROR
F
-
-
STEP2
Status word values
T/F
-
-
For details about the STEP2 status word refer to the STEP2 description
STEP3
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
STEP3
FP_ERROR
F
-
-
STEP3
Status word values
T/F
-
-
For details about the STEP3 status word refer to the STEP3 description
Mathematics
Table of error codes and errors values created for EFBs of the Mathematics family.
EFB name
Error code
ENO state in case of error
Error value in Dec
Error value in Hex
Error description
COMP_DB
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
COMP_DB
FP_ERROR
F
-
-
K_SQRT
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
K_SQRT
FP_ERROR
F
-
-
MULDIV_W
FP_ERROR
F
-
-
SUM_W
FP_ERROR
F
-
-
Measurement
Table of error codes and errors values created for EFBs of the Measurement family.
EFB name
Error code
ENO state in case of error
Error value in Dec
Error value in Hex
Error description
AVGMV
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
AVGMV
W_WARN_AVGMV
T
30108
16#759C
AVGMV: N must be <= 50
AVGMV
FP_ERROR
F
-
-
AVGMV_K
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
AVGMV_K
W_WARN_AVGMV_K
T
30109
16#759D
AVGMV_K: N must be <= 10000
AVGMV_K
FP_ERROR
F
-
-
DEAD_ZONE
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
DEAD_ZONE
E_ERR_DZONE
F
-30119
16#8A59
DZONE: DZ must be >= 0
DEAD_ZONE
FP_ERROR
F
-
-
LOOKUP_TABLE1
E_ERR_DEN
F
-30152
16#8A38
Not a valid floating point number
LOOKUP_TABLE1
E_ERR_POLY_ANZAHL
F
-30107
16#8A65
number of inputs not even
LOOKUP_TABLE1
E_ERR_POLY_FOLGE
F
-30108
16#8A64
base point x(i) <= x(i-1)
LOOKUP_TABLE1
FP_ERROR
F
-
-
Output Processing
Table of error codes and errors values created for EFBs of the Output Processing family.
EFB name
Error code
ENO state in case of error
Error value in Dec
Error value in Hex
Error description
MS
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
MS
FP_ERROR
F
-
-
MS
Status word values
T/F
-
-
For details about the MS status word refer to the MS description
PWM1
WAF_PBM_TMINMAX
F
-30113
16#8A5F
t_min < t_max
PWM1
FP_ERROR
F
-
-
SERVO
FP_ERROR
F
-
-
SERVO
Status word values
T/F
-
-
For details about the SERVO status word refer to the SERVO description
SPLRG
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
SPLRG
E_ERR_NULL_INPUT_SCALE
F
-30121
16#8A57
Null input scale: max and min limit must be different
SPLRG
FP_ERROR
F
-
-
SPLRG
Status word values
T/F
-
-
For details about the SPLRG status word refer to the SPLRG description
Setpoint Management
Table of error codes and errors values created for EFBs of the Setpoint Management family.
EFB name
Error code
ENO state in case of error
Error value in Dec
Error value in Hex
Error description
RAMP
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
RAMP
FP_ERROR
F
-
-
RAMP
Status word values
T/F
-
-
For details about the RAMP status word refer to the RAMP description
RATIO
FP_ERROR
F
-
-
RATIO
Status word values
T/F
-
-
For details about the RATIO status word refer to the RATIO description
SP_SEL
W_WARN_OUT_OF_RANGE
T
30110
16#759E
Parameter out of range
SP_SEL
FP_ERROR
F
-
-
SP_SEL
Status word values
T/F
-
-
For details about the SP_SEL status word refer to the SP_SEL description