Details of the Explicit Exchange Objects for the T_CPT_FLM_IN2-type IODDT
Original instructions
At a Glance
This section presents the explicit exchange objects for the T_CPT_FLM_IN2 - type IODDT which are applicable to the channels of the BMXETM0200H module. They includes word type objects whose bits have a specific meaning. These objects are described in detail below.
NOTE:
  • in general, the meaning of the bits is given for bit status 1.
  • not all bits are used.
Exchange Status: EXCH_STS
The table below presents the bits of the channel exchange status word EXCH_STS (%MWr.m.c.0).
Standard symbol
Type
Access
Meaning
Language object
STS_IN_PROG
BOOL
Read
Status parameter read in progress
%MWr.m.c.0.0
ADJ_IN_PROG
BOOL
Read
Adjust parameter exchange in progress
%Mwr.m.c.0.2
RECONF_IN_PROG
BOOL
Read
Reconfiguration in progress
%MWr.m.c.0.15
Channel Report: EXCH_RPT
The following table presents the bits of the channel exchange word EXCH_RPT (%MWr.m.c.1).
Standard symbol
Type
Access
Meaning
Language object
STS_ERR
BOOL
Read
Error while reading channel status
%MWr.m.c.1.0
ADJ_ERR
BOOL
Read
Error while adjusting the channel
%Mwr.m.c.1.2
RECONF_ERR
BOOL
Read
Error while reconfiguring the channel
%MWr.m.c.1.15
Channel Faults: CH_FLT
The table below presents the bits of the channel faults word CH_FLT (%MWr.m.c.2).
Standard symbol
Type
Access
Meaning
Language object
EXTERNAL_FLT_INPUTS
BOOL
Read
External error on inputs
%MWr.m.c.2.0
EXTERNAL_FLT_OUTPUTS
BOOL
Read
External error on outputs
%MWr.m.c.2.1
INTERNAL_FLT
BOOL
Read
Internal error: channel inoperative
%MWr.m.c.2.4
CONF_FLT
BOOL
Read
Hardware or software configuration error
%MWr.m.c.2.5
COM_FLT
BOOL
Read
Bus communication error
%MWr.m.c.2.6
APPLI_FLT
BOOL
Read
Application error
%MWr.m.c.2.7
Channel Faults Special: CH_FLT_SP
The table below presents the bits of channel faults special word CH_FLT_SP (%MWr.m.c.3).
Standard symbol
Type
Access
Meaning
Language object
SENSOR_SUP_FLT
BOOL
Read
Low input power supply for the sensors
%MWr.m.c.3.2
ACTUATOR_SUP_FLT
BOOL
Read
Low input power supply for the actuator
%MWr.m.c.3.3
MPU_BROKEN_LINE
BOOL
Read
Broken line to MPU detected
%MWr.m.c.3.4
SHORT_CIRCUIT_OUTPUT
BOOL
Read
Output short circuit or overload detected
%MWr.m.c.3.5