Configuration Example
(Original Document)
Introduction
The following example shows the information required to operate a AS-i field device on a 140 EIA 921 00 AS-i Master module using Control Expert.
An inductive proximity switch (type XS1) is connected as Slave 1 and Signal column (type XVB) as Slave 2.
Proximity switch
The following table shows the communication specifications for the inductive proximity switch XS1 M30AS101:
AS-i Profile
S1.1
Bit Status
0
1
Data Bits
Status
D0 (Input)
Signal "Off"
Signal "On"
D1 (Input)
Alarm "On"
Alarm "Off"
D2 (Input)
Not operation ready
Operation ready
D3 (Input)
Not occupied
Not occupied
Command
D0 (Output)
Not occupied
Not occupied
D1 (Output)
Not occupied
Not occupied
D2 (Output)
Not occupied
Not occupied
D3 (Output)
Not occupied
Not occupied
Parameter
P0
Not occupied
Not occupied
P1
Not occupied
Not occupied
P2
Not occupied
Not occupied
P3
Flashing light "On"
Flashing light "Off"
Signal column
The following table shows the communication specifications for the signal column type XV*:
AS-i Profile
S7.F
Bit Status
0
1
Data Bits
Status
D0 (Input)
Not occupied
Not occupied
D1 (Input)
Not occupied
Not occupied
D2 (Input)
Not occupied
Not occupied
D3 (Input)
Not occupied
Not occupied
Command
D0 (Output)
Element 1: "off"
Element 1: "on"
D1 (Output)
Element 2: "off"
Element 2: "on"
D2 (Output)
Element 3: "off"
Element 3: "on"
D3 (Output)
Element 4: "off"
Element 4: "on"
Parameter
P0
Element 1: "Flashing light"
Element 1: "Continuous light"
P1
Element 2: "Flashing light"
Element 2: "Continuous light"
P2
Element 3: "Flashing light"
Element 3: "Continuous light"
P3
Element 4: "Flashing light"
Element 4: "Continuous light"
Addresses and functions
The input signals for the AS-i field device shold be mapped in the input word area %IW101 to %IW113, the output command to the AS-i field device are found in words %MW 201 to %MW209.
The flashing light operational display for the inductive proximity switch should be deactivated.
Elements 2 and 3 of the signal column should be configured as flashing lights, the other elements as continuous lights.
Data transfer
You can transfer the following information from the data sheets for configuring the 140 EIA 921 00:
Parameter configuration
Parameter Configuration Window
Data access
You can take the assignment of the AS-i field device I/O bits to the internal addresses in the Control Expert program from the inputs and outputs mapping table. Word 1 in the input mapping table corresponds to %IW101 and word 1 in the output mapping table corresponds to %MW201.
Input mapping table:
Most significant Byte
Least significant Byte
Word Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Slave Input
D3
D2
D1
D0
D3
D2
D1
D0
D3
D2
D1
D0
D3
D2
D1
D0
Word 1
Slave 3
Slave 2
Slave 1
Not Used
Word 2
Slave 7
Slave 6
Slave 5
Slave 4
...
...
...
...
..
Output mapping table:
Most significant Byte
Least significant Byte
Word Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Slave Output
D3
D2
D1
D0
D3
D2
D1
D0
D3
D2
D1
D0
D3
D2
D1
D0
Word 1
Slave 3
Slave 2
Slave 1
Not Used
Word 2
Slave 7
Slave 6
Slave 5
Slave 4
...
...
...
...
..