AS-i Input
(Original Document)
Inputs
The 140 EIA 921 00 module manages up to 31 slaves. Each slave has 4 inputs. The 124 inputs are assigned by 8 words.
Words 1 to 8 - AS-i Bus Inputs
Words 1 to 8 reflect the input state of the 31 slaves. Bits D3 to D0 correspond to the input data bits for each slave.
Distribution
Most significant byte
Least significant byte
Word bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Slave Input
D3
D2
D1
D0
D3
D2
D1
D0
D3
D2
D1
D0
D3
D2
D1
D0
Word 1
Slave 3
Slave 2
Slave 1
Unused
Word 2
Slave 7
Slave 6
Slave 5
Slave 4
Word 3
Slave 11
Slave 10
Slave 9
Slave 8
Word 4
Slave 15
Slave 14
Slave 13
Slave 12
Word 5
Slave 19
Slave 18
Slave 17
Slave 16
Word 6
Slave 23
Slave 22
Slave 21
Slave 19
Word 7
Slave 27
Slave 26
Slave 25
Slave 24
Word 8
Slave 31
Slave 30
Slave 29
Slave 28
Words 9 to 10 - Active Slaves (LAS)
Words 9 to 10 show the active slaves. A bit value of "1" indicates that the slave is active.
Words
Most significant byte
Least significant byte
Word bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Word 9
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Word 10
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
Words 11 to 12 - Detected Slaves (LDS)
Words 11 to 12 show the slaves detected on the bus. A bit value of "1" indicates that a slave has been detected.
Words
Most significant byte
Least significant byte
Word bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Word 11
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Word 12
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
Words 13 - Status Word
Word 13 contains information on the status.
Words
Most significant byte
Least significant byte
Word 13
D15
D14
D13
D12
D11
D10
D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
D0 - Configuration OK on AS-i bus (software and physical configurations are identical):
1 - OK
0 = NOK
D1 - Slave present with address 0:
1 = present
0 = missing
D2 - Automatic address available:
1= available
0 = unavailable
D3 - Automatic addressing:
1 = automatic assignment of addresses possible
0 = impossible
D4 - Operating mode:
1 = AS-i protected mode
0 = AS-i configuration mode
D5 - Normal operation active:
1 = active
0 = inactive
D6 - AS-i power supply missing:
1 = AS-i power failure
0 = normal power supply for AS-i
D7 - Offline received:
1= AS-i bus in Offline mode
0 = AS-i bus in another mode (not Offline)
D8 - Module diagnostics:
1 = Frozen mode
0 = Exchange of data activated
In order to reactivate the module, you must set the bit D2 of word 9 to 0 (control word of AS-i Output), and then to 1. If the module operates properly when the bit D2 of word 9 is set to 1(control word of AS-i Output), the bit D8 of word 13 (Status word of AS-i Input) must be switched to 0.