Characteristic
|
Value
|
---|---|
AS-i bus maximum cycle time
|
5ms
|
Maximum number of slaves on the AS-i bus
|
31
|
Maximum length of AS-i bus (all branches mixed without repeater)
|
100 meters
|
Maximum number of inputs/outputs
|
124 inputs +124 outputs
|
Nominal supply voltage for AS-i bus
|
30 V DC
|
Characteristic
|
Value
|
---|---|
Programming the TSX SAY 100 module
|
using Control Expert software
|
Response time with 31 slaves (1) for a PLC cycle time of 10 ms
|
Typically 27 ms, 37 ms maximum
|
Calculation of AS-i scanning time for n slaves (normal operation)
|
156 μs x (n+2) if n<31 156 μs x (n+1) if n=31
|
Power consumption 5V PLC
|
Typically 110 mA / 150 mA maximum
|
Power consumption 30 V AS-i
|
Typically 50 mA / 60 mA maximum
|
Power dissipation
|
2.5 W max.
|
Protection from polarity inversion on AS-i bus inputs
|
Yes
|
Degree of protection
|
IP20
|
Operating temperature
|
0 to 60 degrees Celsius
|
AS-i master profile
|
M2
|
Standards and service conditions
|
Compliant with those for Premium PLCs
|
(1) Logical response time + time between an AS-i input activated on the bus, processed in the PLC application and applied to an AS-i output.
|