Characteristics
Original instructions
Altitude Operating Conditions
The characteristics in the tables below apply to the modules BMX AMO 0410 and BMX AMO 0410H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
General Characteristics
The general characteristics for the BMX AMO 0410 and BMX AMO 0410H modules are as follows:
Operating temperature
BMX AMO 0410
0...60 ºC (32...140 ºF)
BMX AMO 0410H
-25...70 ºC (-13...158 ºF)
Type of outputs
High level Fast outputs
Nature of outputs
Voltage or Current configured by software
Number of channels
4
Digital/Analog converter resolution
16 bits
Output refresh time
1 ms
Power supply for outputs
by the module
Types of protection
From short circuits and overloads
(Voltage output)
Isolation:
  • Between channels
  • Between channels and bus
  • Between channels and ground
750 VDC
1400 VDC
1400 VDC
Measurement error for standard module:
  • At 25°C (77°F)
0.10% of FS(1)
  • Maximum in the temperature range 0...60°C (32...140°F)
0.20% of FS(1)
Measurement error for hardened module:
  • At 25°C (77°F)
0.10% of FS(1)
  • Maximum in the temperature range
    -25...70°C (-13...158°F)
0.45% of FS(1)
Temperature drift
45 ppm/°C
Monotonicity
Yes
Common mode rejection (50/60 Hz)
100 dB
Crosstalk between channels DC and AC 50/60Hz
> 80 dB
Non linearity
0.1% of FS(1)
AC output ripple
2 mV rms on 50 Ω
Power consumption (3.3 V)
Typical
0.45 W
Maximum
0.51 W
Power consumption (24 V)
Typical
3.0 W
Maximum
3.6 W
(1) 
FS: Full Scale
Voltage Output
The BMX AMO 0410 and BMX AMO 0410H voltage outputs have the following characteristics:
Nominal variation range
+/-10 V
Maximum variation range
+/- 10.50 V
Analog resolution
0.37 mV
Load impedance
1 KΩ minimum
Detection type
Short circuits
Current Output
The BMX AMO 0410 and BMX AMO 0410H current outputs have the following characteristics:
Nominal variation range
0..20 mA, 4..20 mA
Available maximum current
21 mA
Analog resolution
0.74 µA
Load impedance
500 Ω maximum
Detection type
Open circuit(1)(2)
(1) 
The open circuit detection is physically detected by the module if the target current value is different from 0 mA.
(2) 
Open circuit detection is enabled with the Wiring CTRL parameter.
Response time of Outputs
The maximum delay between transmission of the output value on the PLC bus and its effective positioning on the terminal block is less than 2 ms:
NOTE: If nothing is connected on the BMX AMO 0410 analog module and the channels are configured in the range 4...20 mA, there is a detected I/O error as if a wire is broken.
For the 0...20 mA range, there is a detected I/O error as if a wire is broken only when the current is greater than 0 mA.
CAUTION
RISK OF INCORRECT DATA
If a signal wire is broken or disconnected, the last measured value is kept.
  • Ensure that this does not cause a hazardous situation.
  • Do not rely on the value reported. Check the input value at the sensor.
Failure to follow these instructions can result in injury or equipment damage.