Operating temperature
|
BMX AMI 0810
|
0...60 ºC (32...140 ºF)
|
BMX AMI 0810H
|
-25...70 ºC (-13...158 ºF)
|
|
Type of inputs
|
High level isolated fast inputs
|
|
Nature of inputs
|
Voltage / Current
|
|
Number of channels
|
8
|
|
Acquisition cycle time:
|
|
|
|
1 ms + 1 ms x number of channels used
|
|
|
9 ms
|
|
Display resolution
|
16-bit
|
|
Digital filtering
|
First order
|
|
Isolation:
|
|
|
|
+/-300 VDC
|
|
|
1400 VDC
|
|
|
1400 VDC
|
|
Maximum overload authorized for inputs:
|
Voltage inputs: +/- 30 VDC
Current inputs: +/- 30 mA
Protected against accidental wiring: -19.2 to 30VDC
NOTE: The Protected for accidental wiring function is not supported when the module works with any Telefast interface. |
|
Power consumption (3.3 V)
|
Typical
|
0.32 W
|
Maximum
|
0.48 W
|
|
Power consumption (24 V)
|
Typical
|
1.06 W
|
Maximum
|
1.50 W
|
Measurement range
|
+/- 10 V; +/- 5 V
0...10 V; 0...5 V; 1...5 V
|
+/- 20 mA;
0...20 mA; 4...20 mA
|
---|---|---|
Maximum conversion value
|
+/-11.4 V
|
+/-30 mA
|
Conversion resolution
|
0.36 mV
|
1.4 μA
|
Input impedance
|
10 ΜΩ
|
Internal conversion resistor (250 Ω) + Internal protection resistor (see note)
|
Precision of the internal conversion resistor
|
-
|
0.1% - 15 ppm/°C
|
Measurement errors for standard module :
|
||
|
0.075% of FS(1)
0.1% of FS(1)
|
Typical 0.15% of FS(1)(2)
0.3% of FS(1)(2)
|
Measurement errors for Hardened module:
|
||
|
0.075% of FS(1)
0.2% of FS(1)
|
Typical 0.15% of FS(1)(2)
0.55% of FS(1)(2)
|
Temperature drift
|
30 ppm/°C
|
50 ppm/°C
|
Monotonicity
|
Yes
|
Yes
|
Common mode rejection (50/60 Hz)
|
80 dB
|
80 dB
|
Crosstalk between channels DC and AC 50/60Hz
|
> 80 dB
|
> 80 dB
|
Non-linearity
|
0.001%
|
0.001%
|
Repeatability @25°C of 10 min. stabilization time
|
0.005% of FS(1)
|
0.007% of FS(1)
|
Long term stability after 1000 hours
|
< 0.004% of FS(1)
|
< 0.004% of FS(1)
|
(1)FS: Full Scale (2)With conversion resistor error |