Parameter
|
BMX AMI 0410
|
BMX AMI 0800
|
BMX AMI 0810
|
---|---|---|---|
Number of input channels
|
4
|
8
|
8
|
Channel used (1)
|
Active / Inactive
|
Active / Inactive
|
Active / Inactive
|
Scan Cycle
|
Normal
Fast
|
Normal
Fast
|
Normal
Fast
|
Range
|
+/-10 V
0..0.10 V
0..5 V / 0..20 mA
1..5 V / 4..20 mA
+/- 5V +/- 20mA
|
+/-10 V
0..10 V
0..5 V / 0..20 mA
1..5 V / 4..20 mA
+/- 5V +/- 20mA
|
+/-10 V
0..10 V
0..5 V / 0..20 mA
1..5 V / 4..20 mA
+/- 5V +/- 20mA
|
Filter
|
0..6
|
0..6
|
0..6
|
Display
|
%.. / User
|
%.. / User
|
%.. / User
|
Task associated to Channel
|
MAST / FAST
|
MAST / FAST
|
MAST / FAST
|
Group of channels affected by the task change
|
2 contiguous channels
|
2 contiguous channels
|
2 contiguous channels
|
Rejection
|
-
|
-
|
-
|
Wiring Control (1)
|
-
|
-
|
-
|
Cold junction compensation: channels 0-3
|
N/A
|
N/A
|
N/A
|
Lower Range Overflow Control (1)
|
Active / Inactive
|
Active / Inactive
|
Active / Inactive
|
Upper Range Overflow Control (1)
|
Active / Inactive
|
Active / Inactive
|
Active / Inactive
|
Lower Threshold Range Overflow (1)
|
-11,400
|
-11,400
|
-11,400
|
Upper Threshold Range Overflow (1)
|
11,400
|
11,400
|
11,400
|
(1)This parameter is available as a checkbox. |
Parameter
|
BMX AMM 0600
|
BMX ART 0414
|
BMX ART 0814
|
---|---|---|---|
Number of input channels
|
4
|
4
|
8
|
Channel used (1)
|
Active / Inactive
|
Active / Inactive
|
Active / Inactive
|
Scan Cycle
|
Normal
Fast
|
-
|
-
|
Range
|
+/-10 V
0..0.10 V
0..5 V / 0..20 mA
1..5 V / 4..20 mA
|
Thermo K
Thermocouple B
Thermocouple E
Thermo J
Thermo L
Thermo N
Thermo R
Thermo S
Thermo T
Thermo U
0..400 Ohms
0..4000 Ohms
Pt100 IEC/DIN
Pt1000 IEC/DIN
Pt100 US/JIS
Pt1000 US/JIS
Cu10 Copper
Ni100 IEC/DIN
Ni1000 IEC/DIN
+/- 40 mV
+/- 80 mV
+/- 160 mV
+/- 320 mV
+/- 640 mV
+/- 1.28 V
|
Thermo K
Thermocouple B
Thermocouple E
Thermo J
Thermo L
Thermo N
Thermo R
Thermo S
Thermo T
Thermo U
0..400 Ohms
0..4000 Ohms
Pt100 IEC/DIN
Pt1000 IEC/DIN
Pt100 US/JIS
Pt1000 US/JIS
Cu10 Copper
Ni100 IEC/DIN
Ni1000 IEC/DIN
+/- 40 mV
+/- 80 mV
+/- 160 mV
+/- 320 mV
+/- 640 mV
+/- 1.28 V
|
Filter
|
0..6
|
0..6
|
0..6
|
Display
|
%.. / User
|
1/10 °C / 1/10 °F / %.. / User
|
1/10 °C / 1/10 °F / %.. / User
|
Task associated to Channel
|
MAST / FAST
|
MAST
|
MAST
|
Group of channels affected by the task change
|
2 contiguous channels
|
2 contiguous channels
|
2 contiguous channels
|
Rejection
|
-
|
50 Hz / 60 Hz
|
50 Hz / 60 Hz
|
Wiring Control (1)
|
-
|
Active / Inactive
|
Active / Inactive
|
Cold junction compensation: channels 0-3
|
N/A
|
|
|
Lower Range Overflow Control (1)
|
Active / Inactive
|
Active / Inactive
|
Active / Inactive
|
Upper Range Overflow Control (1)
|
Active / Inactive
|
Active / Inactive
|
Active / Inactive
|
Lower Threshold Range Overflow (1)
|
-11,250
|
-2,680
|
-2,680
|
Upper Threshold Range Overflow (1)
|
11,250
|
13,680
|
13,680
|
(1)This parameter is available as a checkbox. |