Parameters for Analog Input Modules
Original instructions
At a Glance
Analog input modules include channel-specific parameters displayed in the module configuration screen.
Reference
The available parameters for each analog input module are as follows (parameters indicated in bold characters are part of the default configuration).
Parameter
BMX AMI 0410
BMX AMI 0800
BMX AMI 0810
Number of input channels
4
8
8
Channel used (1)
Active / Inactive
Active / Inactive
Active / Inactive
Scan Cycle
Normal
Fast
Normal
Fast
Normal
Fast
Range
+/-10 V
0..0.10 V
0..5 V / 0..20 mA
1..5 V / 4..20 mA
+/- 5V +/- 20mA
+/-10 V
0..10 V
0..5 V / 0..20 mA
1..5 V / 4..20 mA
+/- 5V +/- 20mA
+/-10 V
0..10 V
0..5 V / 0..20 mA
1..5 V / 4..20 mA
+/- 5V +/- 20mA
Filter
0..6
0..6
0..6
Display
%.. / User
%.. / User
%.. / User
Task associated to Channel
MAST / FAST
MAST / FAST
MAST / FAST
Group of channels affected by the task change
2 contiguous channels
2 contiguous channels
2 contiguous channels
Rejection
-
-
-
Wiring Control (1)
-
-
-
Cold junction compensation: channels 0-3
N/A
N/A
N/A
Lower Range Overflow Control (1)
Active / Inactive
Active / Inactive
Active / Inactive
Upper Range Overflow Control (1)
Active / Inactive
Active / Inactive
Active / Inactive
Lower Threshold Range Overflow (1)
-11,400
-11,400
-11,400
Upper Threshold Range Overflow (1)
11,400
11,400
11,400
(1) 
This parameter is available as a checkbox.
Parameter
BMX AMM 0600
BMX ART 0414
BMX ART 0814
Number of input channels
4
4
8
Channel used (1)
Active / Inactive
Active / Inactive
Active / Inactive
Scan Cycle
Normal
Fast
-
-
Range
+/-10 V
0..0.10 V
0..5 V / 0..20 mA
1..5 V / 4..20 mA
Thermo K
Thermocouple B
Thermocouple E
Thermo J
Thermo L
Thermo N
Thermo R
Thermo S
Thermo T
Thermo U
0..400 Ohms
0..4000 Ohms
Pt100 IEC/DIN
Pt1000 IEC/DIN
Pt100 US/JIS
Pt1000 US/JIS
Cu10 Copper
Ni100 IEC/DIN
Ni1000 IEC/DIN
+/- 40 mV
+/- 80 mV
+/- 160 mV
+/- 320 mV
+/- 640 mV
+/- 1.28 V
Thermo K
Thermocouple B
Thermocouple E
Thermo J
Thermo L
Thermo N
Thermo R
Thermo S
Thermo T
Thermo U
0..400 Ohms
0..4000 Ohms
Pt100 IEC/DIN
Pt1000 IEC/DIN
Pt100 US/JIS
Pt1000 US/JIS
Cu10 Copper
Ni100 IEC/DIN
Ni1000 IEC/DIN
+/- 40 mV
+/- 80 mV
+/- 160 mV
+/- 320 mV
+/- 640 mV
+/- 1.28 V
Filter
0..6
0..6
0..6
Display
%.. / User
1/10 °C / 1/10 °F / %.. / User
1/10 °C / 1/10 °F / %.. / User
Task associated to Channel
MAST / FAST
MAST
MAST
Group of channels affected by the task change
2 contiguous channels
2 contiguous channels
2 contiguous channels
Rejection
-
50 Hz / 60 Hz
50 Hz / 60 Hz
Wiring Control (1)
-
Active / Inactive
Active / Inactive
Cold junction compensation: channels 0-3
N/A
  • Internal by TELEFAST,
  • External by PT100.
  • Internal by TELEFAST,
  • External by PT100,
  • Using the CJC values of channels 4/7 for channels 0/3.
Lower Range Overflow Control (1)
Active / Inactive
Active / Inactive
Active / Inactive
Upper Range Overflow Control (1)
Active / Inactive
Active / Inactive
Active / Inactive
Lower Threshold Range Overflow (1)
-11,250
-2,680
-2,680
Upper Threshold Range Overflow (1)
11,250
13,680
13,680
(1) 
This parameter is available as a checkbox.